| Plan Review Notes For Permit 21110616 |
| Permit Number |
21110616 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-23 10:26:58 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21110616 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ADDRESS ON THE APPLICATION IS 1249 PALM BEACH | | | LAKES BLVD. BUT THE ADDRESS ON THE HOOD DRAWINGS IS | | | 1225 PALM BEACH LAKES BLVD. PLEASE CORRECT. | | | | | | 2) SHEET 5 OF 8 INDICATES A EF-5 AT 600 CFM?S OF | | | EXHAUST. THE ORIGINAL PLANS DO NOT SHOW THIS EF-5 NOR | | | DOES IT APPEAR ON THE AIR BALANCE REPORT. PLEASE SHOW | | | THIS EF-5 AND WHAT IT IS EXHAUSTING. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|