| 2022-03-09 10:49:34 | 2ND REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 21110596 |
| | 3/9/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A WRITTEN SCOPE OF GAS WORK ON THE |
| | PLAN FOR CLARIFICATION- SEC. 107.2.1 WPB. CLARIFY IF |
| | ANY GAS PIPING, GAS APPLIANCES, SHUTOFFS, REGULATORS |
| | ETC. ARE BEING REPLACED OR RELOCATED. A GAS RISER MAY |
| | BE REQUIRED AS OUTLINED BELOW. |
| | |
| | REFER TO SECS. G2412.3 & G2412.4 FBC RES |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | |
| | 2) 2ND REQUEST TO PROVIDE A GAS SUB- PERMIT- SEC 105.1 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |