| 2022-03-17 10:47:40 | ELECTRIC REVIEW FAILED |
| | 1) PLANS NEED TO PROVIDE MORE CLARITY. PLEASE PROVIDE A |
| | FLOOR PLAN THAT INCLUDES ELECTRIC WORK ONLY. PLEASE |
| | PROVIDE AN ELECTRIC ONLY WORK SCOPE. FBC 107.2 |
| | 2 )PLEASE DETAIL ON DRAWING COMPLIANCE WITH ANY OF THE |
| | APPLICABLE NEC REQUIREMENTS INCLUDING BUT NOT LIMITED |
| | TO THE FOLLOWING: |
| | A) NEC 210.8 GFCI PROTECTION |
| | B) NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION |
| | C) NEC 220.52 RECEPTACLE SPACING |
| | D) NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT |
| | RECEPTACLES |
| | E) NEC 250.140 RANGE GROUNDING |
| | F) SMOKE/CARBON ALARMS AS PER FBC 553.883 |
| | G) PLEASE PROVIDE SPECIFICATIONS OF NEW LIGHTS. THEY |
| | ARE STATED AS LOW VOLTAGE. WILL THIS BE LOW VOLTAGE |
| | WIRING? WHERE WILL THE LED DRIVER BE LOCATED? IF LOW |
| | VOLTAGE WIRING, PLEASE DETAIL WIRE TYPE AND INDICATE |
| | WHETHER CEILING IS A PLENUM |
| | 3) PLEASE HAVE THE CONTRACTOR OR QUALIFIER WHO PREPARED |
| | THE DRAWING PROVIDE HIS/HER SIGNATURE ON IT- SECTION |
| | 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) & |
| | 471.025. SURVEYOR SEAL STATUTE 472.025 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |