| Plan Review Notes For Permit 21110572 |
| Permit Number |
21110572 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-07 10:15:57 | 1ST REVIEW FMC | | | PERMIT: 21110572 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE ADD DUCT SIZES TO EACH DUCT. FBC 107.2.1 | | | | | | 2) PLEASE LABEL THE RED IN THE CORNER OF BEDROOM 2. FBC | | | 107.2.1 | | | | | | 3) PLEASE SHOW THE EXISTING CONDENSING UNITS ORIGINAL | | | LOCATION AND THE LOT LINE AT THE NEW LOCATION. FBC | | | 107.2.1 | | | | | | 4) THE CONTRACT SUBMITTED WITH THIS PROJECT STATES | | | SCOPE OF WORK. PLEASE SHOW EACH OF THE ITEMS ON THE | | | MECHANICAL DRAWING. FBC 107.2.1 | | | | | | 5) PLEASE SHOW HOW THE DUCT FOR THE MASTER BEDROOM WILL | | | BE WEATHER PROOF ON THE ROOF. FBC 107.2.1 | | | | | | 6) IS THE WATER HEATER A NEW INSTALLATION? IF SO A | | | PERMIT FOR THE GAS WORK WILL BE REQUIRED. | | | | | | 7) PLEASE PROVIDE DETAILS FOR THE VENT FOR THE WATER | | | HEATER. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|