Plan Review Notes
Plan Review Notes For Permit 21110549
Permit Number 21110549
Review Stop E
Sequence Number 1
Notes
Date Text
2021-12-16 14:40:54ELECTRICAL PLAN REVIEW FAILED
 1) LOAD CALCULATION TO INCLUDE MAIN ELECTRIC PANEL AND
 NEW SUB PANEL NEC 215.2
 2) LOAD CALCULATIONS SHALL INCLUDE ALL LOADS SERVED.
 NEC 220.40
 3) GROUNDING ELECTRODE SYSTEM REQUIRED AT COTTAGE. NEC
 250.32
 4) ELECTRIC RISER STATES UNDERSIZED WIRE FEEDING
 COTTAGE. NEC 310.15(B)
 5) ELECTRIC RISER DOES NOT INCLUDE EQUIPEMENT BONDING
 JUMPER IN FEEDER CONDUIT.NEC 250.32 (B) (1)
 6) RECEPTACLE REQUIRED AT OUTSIDE PORCH/BALCONY. NEC
 210.52(E)(3)
 7) ELECTRICAL RISER DOES NOT STATE SIZE AND OVERCURRENT
 PROTECTION FOR SUB PANEL F.B.C.107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved