| 2021-12-16 14:40:54 | ELECTRICAL PLAN REVIEW FAILED |
| | 1) LOAD CALCULATION TO INCLUDE MAIN ELECTRIC PANEL AND |
| | NEW SUB PANEL NEC 215.2 |
| | 2) LOAD CALCULATIONS SHALL INCLUDE ALL LOADS SERVED. |
| | NEC 220.40 |
| | 3) GROUNDING ELECTRODE SYSTEM REQUIRED AT COTTAGE. NEC |
| | 250.32 |
| | 4) ELECTRIC RISER STATES UNDERSIZED WIRE FEEDING |
| | COTTAGE. NEC 310.15(B) |
| | 5) ELECTRIC RISER DOES NOT INCLUDE EQUIPEMENT BONDING |
| | JUMPER IN FEEDER CONDUIT.NEC 250.32 (B) (1) |
| | 6) RECEPTACLE REQUIRED AT OUTSIDE PORCH/BALCONY. NEC |
| | 210.52(E)(3) |
| | 7) ELECTRICAL RISER DOES NOT STATE SIZE AND OVERCURRENT |
| | PROTECTION FOR SUB PANEL F.B.C.107.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |