| Plan Review Notes For Permit 21110547 |
| Permit Number |
21110547 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-21 16:43:07 | ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE OCCUPANCY CLASSIFICATION FOR THE NEW | | | SPACE - FBC 508.2.1 | | | | | | 2) BUILDING CONSTRUCTION TYPE IS SHOWN ON THE DRAWINGS | | | AS IIB - PLEASE SHOW THE PLYWOOD ADDED TO THE WALLS AS | | | "FIRE RETARDANT" PER FBC 603.1 | | | | | | 3) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVAL FOR THE NEW EXTERIOR DOORS - ALL | | | PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE DESIGNER OF RECORD (ARCHITECT OR | | | ENGINEER) FBC WPB 107.3.4 | | | | | | 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE REAR TOILET | | | GRAB BAR DIMENSIONS FROM THE CENTER OF THE TOILET PER | | | FBC A 604.5.2 | | | | | | 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE DOOR | | | MANEUVERING SPACE TO EXIT THE RESTROOM (18" BESIDE THE | | | DOOR) FBC A 404.2.4 |
|