| 2021-11-16 12:19:14 | 11/16/21 1 ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WOULD YOU PLEASE HAVE A SIGNATURE ON THE ISOMETRIC |
| | DRAWING OF THE PERSON DESIGNING THE SYSTEM, NOT IN |
| | ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.1 GENERAL. |
| | |
| | 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| | CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. THE APPLICATION FOR THE SCOPE OF WORK MENTIONED AN |
| | EXISTING SYSTEM. THE CITY OF WEST PALM BEACH HAS NO |
| | RECORD OF EXISTING GAS PERMITS WITH INSPECTIONS OF THE |
| | CURRENT SYSTEM. PLEASE INCLUDE THE CURRENT AND NEW GAS |
| | SYSTEM AND EQUIPMENT IN THIS PERMIT FOR THIS SCOPE OF |
| | WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 4. THE GAS FOR THE REAR UNIT NEEDS A SEPARATE PERMIT |
| | AND APPLICATION FROM THE FRONT UNIT, AND THE GAS HEATER |
| | SEEMS TO BELONG TO THE FRONT UNIT. THESE ARE CONSIDERED |
| | TWO DETACHED DWELLINGS, AND THERE NEED TO BE TWO |
| | SEPARATE METERS. WOULD YOU PLEASE SEPARATE THE UNITS |
| | AND HAVE A SEPARATE PERMIT THAT ADDRESSES THE COMMENTS |
| | BELOW FOR THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 105.1. |
| | |
| | 5. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS |
| | FOR ALL GAS EQUIPMENT FUTURE AND NEW PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 6. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. GAS UNITS MAY REQUIRE CONDENSATE, AND THEY NEED TO |
| | BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC |
| | R318.5. A NOTE ON ISO WILL BE OK. |
| | |
| | 8. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| | 403.5.3. A NOTE ON ISO WILL BE OK. |
| | |
| | 9. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. PLEASE SHOW THE REGULATOR |
| | ON ISO. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| | BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER |
| | THE 2020 FBC RES. SEC. G2421.1. |
| | |
| | 10. WOULD YOU PLEASE LABEL AND SHOW ALL UNIONS IN FRONT |
| | OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES? |
| | SEC G2421.2. |
| | |
| | 11. WOULD YOU PLEASE SHOW AND LABEL THE VALVES ON THE |
| | GAS ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC |
| | RES. SEC. G2420.5. |
| | |
| | 12. THE SHUT-OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| | GD, ACCESS. A NOTE ON ISO WILL BE OK. |
| | |
| | 13. WOULD YOU PLEASE SHOW AND LABEL DRIP LEG ON |
| | EQUIPMENT INSTALLED, EXCEPT FOR APPLIANCES, RANGE, |
| | DRYERS & OD GRILLS PER THE 2020 FBC FG 408.2 OR 2020 |
| | FBC RES. SEC. G2419.2. |
| | |
| | 14. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC |
| | RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 15. NEED A HARD CAP FOR FUTURE RANGE SHOW ON GAS |
| | ISOMERIC SHUTOFF 2020 FBC RES. SEC. G2401.1.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |