Plan Review Notes
Plan Review Notes For Permit 21110533
Permit Number 21110533
Review Stop G
Sequence Number 1
Notes
Date Text
2021-11-16 12:19:1411/16/21 1 ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE HAVE A SIGNATURE ON THE ISOMETRIC
 DRAWING OF THE PERSON DESIGNING THE SYSTEM, NOT IN
 ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.1 GENERAL.
  
 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP
 CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. THE APPLICATION FOR THE SCOPE OF WORK MENTIONED AN
 EXISTING SYSTEM. THE CITY OF WEST PALM BEACH HAS NO
 RECORD OF EXISTING GAS PERMITS WITH INSPECTIONS OF THE
 CURRENT SYSTEM. PLEASE INCLUDE THE CURRENT AND NEW GAS
 SYSTEM AND EQUIPMENT IN THIS PERMIT FOR THIS SCOPE OF
 WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 4. THE GAS FOR THE REAR UNIT NEEDS A SEPARATE PERMIT
 AND APPLICATION FROM THE FRONT UNIT, AND THE GAS HEATER
 SEEMS TO BELONG TO THE FRONT UNIT. THESE ARE CONSIDERED
 TWO DETACHED DWELLINGS, AND THERE NEED TO BE TWO
 SEPARATE METERS. WOULD YOU PLEASE SEPARATE THE UNITS
 AND HAVE A SEPARATE PERMIT THAT ADDRESSES THE COMMENTS
 BELOW FOR THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO
 THE FBC SEC. 105.1.
  
 5. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS
 FOR ALL GAS EQUIPMENT FUTURE AND NEW PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. GAS UNITS MAY REQUIRE CONDENSATE, AND THEY NEED TO
 BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC
 R318.5. A NOTE ON ISO WILL BE OK.
  
 8. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. A NOTE ON ISO WILL BE OK.
  
 9. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. PLEASE SHOW THE REGULATOR
 ON ISO. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER
 THE 2020 FBC RES. SEC. G2421.1.
  
 10. WOULD YOU PLEASE LABEL AND SHOW ALL UNIONS IN FRONT
 OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES?
 SEC G2421.2.
  
 11. WOULD YOU PLEASE SHOW AND LABEL THE VALVES ON THE
 GAS ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC
 RES. SEC. G2420.5.
  
 12. THE SHUT-OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS. A NOTE ON ISO WILL BE OK.
  
 13. WOULD YOU PLEASE SHOW AND LABEL DRIP LEG ON
 EQUIPMENT INSTALLED, EXCEPT FOR APPLIANCES, RANGE,
 DRYERS & OD GRILLS PER THE 2020 FBC FG 408.2 OR 2020
 FBC RES. SEC. G2419.2.
  
 14. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 15. NEED A HARD CAP FOR FUTURE RANGE SHOW ON GAS
 ISOMERIC SHUTOFF 2020 FBC RES. SEC. G2401.1.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  