| Plan Review Notes For Permit 21110524 |
| Permit Number |
21110524 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-03-31 14:46:49 | 4/7/22 CLIENT DIRECTED ME TO SPECS IN SUBMITTAL THAT I | | | MISSED, CHANGED THE RESULT TO PASS. MP | | | | | | ELECTRIC REVIEW FAILED | | | 1) IT APPEARS USING THE RATINGS GIVEN, 280 WATTS , 2.33 | | | AMPS, THAT MOTORS DETAILED ON PLAN E-01 AS LOW VOLTAGE, | | | ARE 120-VOLT. PLEASE DETAIL AN NEC COMPLIANT WIRING | | | METHOD TO PROTECT THESE CONDUCTORS FEEDING THESE | | | MOTORS. FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | | | | | | | |
|