| 2021-12-15 13:42:35 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:21110524 |
| | W. P. B. MASTER: 21071035 |
| | ADD: 700 S. ROSEMARY AVE. # 232 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-414-2190 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 15TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT ISSUANCE FOR CITY PLACE |
| | REQUIRE CITY PLACE MANAGEMENT STAMP OF REVIEW AND |
| | APPROVAL BEFORE PERMIT ISSUANCE CAN OCCUR. 107.2.1.2. |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2) THE COVERSHEET LIST THE MEAN ROOF HEIGHT AS 9 FT. |
| | THIS IS ON THE 2ND FLOOR, THE 2ND FLOOR JUST TO THE |
| | NORTH OF THIS LOCATION IS HIGH ENOUGH THAT THE 2ND |
| | FLOOR DECK ACTUALLY PASSES OVER THE STREET BELOW. |
| | PLEASE UPDATE THE ELEVATION AND HEIGHT MULTIPLIERS FOR |
| | PRESSURES. |
| | |
| | 3) WELDING ON JOBSITE. WELDED OR BOLTED CONNECTIONS. |
| | THIS BUILDING CONTAINS EITHER BOLTED AND OR WELDED |
| | CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR |
| | RICHARD BRUNELLE AT 561-805-6670. |
| | |
| | 4) SHEETS S-04 AND OR A-06 (SCREENS). THERE IS NO |
| | INFORMATION FOR COMPLIANCE WITH 2020 FBC-B SECTION |
| | 3105.3.4.1. FABRIC USED FOR AWNINGS OR FABRIC COVERED |
| | FRAMES SHALL MEET THE FLAME PROPAGATION PERFORMANCE |
| | CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD INDEX NOT |
| | GREATER THAN 25 WHEN TESTED IN ACCORDANCE WITH ASTM E84 |
| | OR UL 723. |
| | |
| | 5A) RIGID FRAME AWNINGS/ BREAK AWAY FABRIC. FBC-B |
| | 3105.4.2.1. DESIGN. THE WIND DESIGN LOADS FOR ANY |
| | FABRIC OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH A |
| | QUICK REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING |
| | CRITERIA: |
| | 1) MINIMUM WIND SPEED OF 105 MPH |
| | 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16. |
| | |
| | 5B) RIGID AWNING. PERMANENT OR NON-REMOVABLE FABRIC. |
| | FBC-B 3105.4.2.2. THE WIND DESIGN LOADS FOR ANY FABRIC |
| | OR MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT |
| | OR NON-REMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON |
| | THE FOLLOWING CRITERIA: |
| | 1) MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER |
| | 16 USING FIGURE 1609.3(3) 150 VULT, CATEGORY 1 |
| | BUILDINGS. |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |