2021-12-15 13:42:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21110524
 W. P. B. MASTER: 21071035
 ADD: 700 S. ROSEMARY AVE. # 232
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-414-2190
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 15TH/ 2021
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT ISSUANCE FOR CITY PLACE
 REQUIRE CITY PLACE MANAGEMENT STAMP OF REVIEW AND
 APPROVAL BEFORE PERMIT ISSUANCE CAN OCCUR. 107.2.1.2.
 ADDITIONAL INFORMATION REQUIRED.
  
 2) THE COVERSHEET LIST THE MEAN ROOF HEIGHT AS 9 FT.
 THIS IS ON THE 2ND FLOOR, THE 2ND FLOOR JUST TO THE
 NORTH OF THIS LOCATION IS HIGH ENOUGH THAT THE 2ND
 FLOOR DECK ACTUALLY PASSES OVER THE STREET BELOW.
 PLEASE UPDATE THE ELEVATION AND HEIGHT MULTIPLIERS FOR
 PRESSURES.
  
 3) WELDING ON JOBSITE. WELDED OR BOLTED CONNECTIONS.
 THIS BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 4) SHEETS S-04 AND OR A-06 (SCREENS). THERE IS NO
 INFORMATION FOR COMPLIANCE WITH 2020 FBC-B SECTION
 3105.3.4.1. FABRIC USED FOR AWNINGS OR FABRIC COVERED
 FRAMES SHALL MEET THE FLAME PROPAGATION PERFORMANCE
 CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD INDEX NOT
 GREATER THAN 25 WHEN TESTED IN ACCORDANCE WITH ASTM E84
 OR UL 723.
  
 5A) RIGID FRAME AWNINGS/ BREAK AWAY FABRIC. FBC-B
 3105.4.2.1. DESIGN. THE WIND DESIGN LOADS FOR ANY
 FABRIC OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH A
 QUICK REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1) MINIMUM WIND SPEED OF 105 MPH
 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16.
  
 5B) RIGID AWNING. PERMANENT OR NON-REMOVABLE FABRIC.
 FBC-B 3105.4.2.2. THE WIND DESIGN LOADS FOR ANY FABRIC
 OR MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT
 OR NON-REMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON
 THE FOLLOWING CRITERIA:
 1) MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER
 16 USING FIGURE 1609.3(3) 150 VULT, CATEGORY 1
 BUILDINGS.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER