Plan Review Notes
Plan Review Notes For Permit 21110519
Permit Number 21110519
Review Stop P
Sequence Number 1
Notes
Date Text
2022-03-04 12:06:1403/04/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-1, IT SHOWS A P TRAP FOR A 2" DRIP, AND
 IT REQUIRES A TRAP SEAL PROTECTION PER THE 2020 FBC
 SEC. 1002.4.1 TRAP SEAL PROTECTION.
  
 2. THE DRAWING ON THE TANK-LESS ONLY SHOWS TWO TANKS
 AND THREE IN THE SCOPE OF WORK. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. GAS UNITS REQUIRE CONDENSATE, AND THEY NEED TO BE 1'
 AWAY FROM THE STRUCTURE TO A SAFE LOCATION PER THE 2020
 FBC SEC R318.5.
  
 4. WOULD YOU PLEASE SUBMIT ON THE PLAN THE LOCATION OF
 THE TANK-LESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER? THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. WOULD YOU PLEASE IDENTIFY ALL GAS APPLIANCES ON
 PLANS TO REFLECT GAS ISOMETRIC WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER
 DIAGRAM FOR WATER PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. THE HOT WATER
 LINES NEED TO BE LOOPED FOR THE RECIRCULATING SYSTEM IN
 A CONTINUOUS LOOP. THERE IS A REQUIREMENT IN THE
 FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A TABLE
 THAT LIMITS THE BETWEEN THE SOURCE AND THE OUTLET;
 PLEASE REFER TO TABLE 404.5.1 FOR THE MAXIMUM ALLOWABLE
 PIPE LENGTH METHOD AND SIZE ACCORDANTLY.
  
 7. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  