| Plan Review Notes For Permit 21110519 |
| Permit Number |
21110519 |
|
| Review Stop |
NFIP |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-24 15:45:25 | NFIP REVIEW COMMENTS | | | | | | THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS SITE IS AE | | | WITH A BASE FLOOD ELEVATION (BFE) OF 6'0" NAVD AND 7'0" | | | NAVD, | | | THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO. | | | 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD. | | | THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE | | | 9'0" NAVD. | | | | | | | | | PLEASE REFERENCE PLAN PAGE A1.10 FOR THE FOLLOWING | | | COMMENTS: | | | | | | 4A) PROVIDE MODEL NUMBER OF VENT TO BE INSTALLED. | | | 4B) STATE SQ/IN OF VENT AND HOW MUCH FLOOR AREA IT WILL | | | COVER. | | | 4C) PLACE THE SF OF GARAGE FLOOR ON PLAN (579SF) | | | 4D) A/C EQUIPMENT SHALL BE AT OR ABOVE THE DESIGN FLOOD | | | ELEVATION OF 9'0" NAVD. | | | | | | 5. PLAN PAGE S-1 DOES NOT SHOW THE THIRD VENT INSTALLED | | | ON AN ADJACENT WALL. | | | | | | 6. LINE B1, NFIP COMMUNITY NAME AND NUMBER IS | | | INCORRECT. | | | | | | 7. LINE C1, THIS IS A CONSTRUCTION DRAWING EC. | | | | | | 8. ENTER CORRECT DATA FOR LINES C2A THRU C2H. | | | | | | 9. REMOVE PHOTOS OF AN EXISTING STRUCTURE. NOT | | | APPLICABLE FOR A CONSTRUCTION DRAWING EC. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. |
|