Plan Review Notes
Plan Review Notes For Permit 21110519
Permit Number 21110519
Review Stop G
Sequence Number 1
Notes
Date Text
2022-03-04 13:20:0803/04/22 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-2, A SECTION OF METAL PIPE FROM THE METER
 TO THE GENERATOR SEEMS TO BE UNDERGROUND, AND ZINC
 COATING SHALL NOT BE DEEMED ADEQUATE PROTECTION FOR
 UNDERGROUND GAS PIPING PER THE 20230 FBC G2415.11.1.
  
 2. WOULD YOU PLEASE PROVIDE THE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC RES. SEC.
 G2408.1.
  
 3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 4. WOULD YOU PLEASE LABEL AND SHOW ALL UNIONS IN FRONT
 OF REGULATOR 1' OF EITHER SIDE PER THE 2 2020 FBC RES.
 SEC G2421.2.
  
 5. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC
 RES. SEC. G2420.5.
  
 6. A GRILL ON THE ISOMETRIC IS NOT SHOWN ON THE
 ARCHITECTURAL. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 7. A GAS GRILL IS SHOWN ON THE ISOMETRIC BUT IS IT FOR
 OUTDOOR USE, AND IS IT UNDER A COVERED PATIO; IF SO,
 PLEASE PROVIDE MANUFACTURERS RECOMMENDATION FOR A
 VENTILATION HOOD PER THE 2020 FBC RES. SEC. G2408.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  