| Plan Review Notes For Permit 21110514 |
| Permit Number |
21110514 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-22 15:54:19 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21110514 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC | | | 101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC R403.7 | | | | | | 3) PLEASE SHOW THE CONDENSATE LINE MATERIAL, SIZE AND | | | TERMINATION LOCATION. FBC RES M1411.3 | | | | | | 4) PLEASE SHOW THE DRYER EXHAUST DUCT AND TERMINATION | | | LOCATION. FBC RES M1502 | | | | | | 5) PLEASE SHOW THE BATH EXHAUST FAN, DUCT AND | | | TERMINATION LOCATION FOR BEDROOM BATH 1. FBC RES | | | M1507.4 | | | | | | 6) PLEASE PROVIDE THE CFM?S OF EXHAUST FOR THE KITCHEN | | | HOOD. DOES IT REQUIRE MAKE UP AIR? FBC RES M1503.4 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|