| Date |
Text |
| 2022-01-14 16:33:22 | BUILDING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: 1/4/22 VALUE ADJUSTED TO $291,569.00 BASED ON |
| | THE ICC BUILDING VALUATION DATA. CT |
| | |
| | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDY LINE SURVEY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. FINISH FLOOR ELEVATION NON-FLOOD ZONE |
| | R403.1.7.3 FOUNDATION ELEVATION. |
| | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION |
| | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER |
| | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED |
| | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 |
| | PERCENT. |
| | ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO THE |
| | APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN BE |
| | DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF |
| | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| | ALL LOCATIONS ON THE SITE. |
| | NOTE: 18" ABOVE CROWN OF THE ROAD IS NOT APPLICABLE. |
| | |
| | 3. PROVIDE AN ENERGY SUBMITTAL. |
| | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| | STORIES. |
| | FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE |
| | ALTERNATIVE. |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | 4. OHD IS MISLABLED ON FLOOR PLAN. DOOR SCHEDULE LEGEND |
| | SHOWS THE OHD AS DOOR #8. PLEASE CLARIFY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 5. PROVIDE A PRODUCT APPROVAL FOR EXT. STEEL DOOR #2. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |