| 2023-06-28 14:21:34 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THERE ARE THREE DRAWING THAT WERE UPLOADED. THE |
| | FIRST TWO SHOW THE LIFT CHAIR CAN BE PARKED OFF OF THE |
| | STAIRWAY AND THE THIRD DRAWING SHOWS IT PARKED ON THE |
| | STAIRWAY. INDICATE WHICH OF THE DRAWINGS ARE CORRECT. |
| | FBC 107.2.1 |
| | |
| | 2) THERE IS A CONCERN THAT THE CHAIR MAY INFRINGE ON |
| | THE REQUIRED STAIRWAY WIDTH FOR EGRESS. SHOW COMPLIANCE |
| | WITH FBC1011.2 WIDTH AND CAPACITY. THE REQUIRED |
| | CAPACITY OF STAIRWAYS SHALL BE DETERMINED AS SPECIFIED |
| | IN SECTION 1005.1, BUT THE MINIMUM WIDTH SHALL BE NOT |
| | LESS THAN 44 INCHES (1118 MM). SEE SECTION 1009 FOR |
| | ACCESSIBLE MEANS OF EGRESS STAIRWAYS. |
| | EXCEPTIONS: |
| | (1) STAIRWAYS SERVING AN OCCUPANT LOAD OF LESS THAN 50 |
| | SHALL HAVE A WIDTH OF NOT LESS THAN 36 INCHES (914 MM). |
| | (2) SPIRAL STAIRWAYS AS PROVIDED FOR IN SECTION |
| | 1011.10. |
| | (3) WHERE AN INCLINE PLATFORM LIFT OR STAIRWAY |
| | CHAIRLIFT IS INSTALLED ON STAIRWAYS SERVING OCCUPANCIES |
| | IN GROUP R-3, OR WITHIN DWELLING UNITS IN OCCUPANCIES |
| | IN GROUP R-2, A CLEAR PASSAGE WIDTH NOT LESS THAN 20 |
| | INCHES (508 MM) SHALL BE PROVIDED. WHERE THE SEAT AND |
| | PLATFORM CAN BE FOLDED WHEN NOT IN USE, THE DISTANCE |
| | SHALL BE MEASURED |
| | FROM THE FOLDED POSITION. |
| | |
| | 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |