 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE THREE DRAWING THAT WERE UPLOADED. THE
 FIRST TWO SHOW THE LIFT CHAIR CAN BE PARKED OFF OF THE
 STAIRWAY AND THE THIRD DRAWING SHOWS IT PARKED ON THE
 STAIRWAY. INDICATE WHICH OF THE DRAWINGS ARE CORRECT.
 FBC 107.2.1
  
 2) THERE IS A CONCERN THAT THE CHAIR MAY INFRINGE ON
 THE REQUIRED STAIRWAY WIDTH FOR EGRESS. SHOW COMPLIANCE
 WITH FBC1011.2 WIDTH AND CAPACITY. THE REQUIRED
 CAPACITY OF STAIRWAYS SHALL BE DETERMINED AS SPECIFIED
 IN SECTION 1005.1, BUT THE MINIMUM WIDTH SHALL BE NOT
 LESS THAN 44 INCHES (1118 MM). SEE SECTION 1009 FOR
 ACCESSIBLE MEANS OF EGRESS STAIRWAYS.
 EXCEPTIONS:
 (1) STAIRWAYS SERVING AN OCCUPANT LOAD OF LESS THAN 50
 SHALL HAVE A WIDTH OF NOT LESS THAN 36 INCHES (914 MM).
 (2) SPIRAL STAIRWAYS AS PROVIDED FOR IN SECTION
 1011.10.
 (3) WHERE AN INCLINE PLATFORM LIFT OR STAIRWAY
 CHAIRLIFT IS INSTALLED ON STAIRWAYS SERVING OCCUPANCIES
 IN GROUP R-3, OR WITHIN DWELLING UNITS IN OCCUPANCIES
 IN GROUP R-2, A CLEAR PASSAGE WIDTH NOT LESS THAN 20
 INCHES (508 MM) SHALL BE PROVIDED. WHERE THE SEAT AND
 PLATFORM CAN BE FOLDED WHEN NOT IN USE, THE DISTANCE
 SHALL BE MEASURED
 FROM THE FOLDED POSITION.
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  