Plan Review Notes
Plan Review Notes For Permit 21110486
Permit Number 21110486
Review Stop G
Sequence Number 3
Notes
Date Text
2022-01-25 11:12:073RD REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21110486
 1/25/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS- DENIED.
  
 1) GAS RISER CORRECTIONS- SECS. G2412.3 & G2412.4 FBC
 FG: A) THE BRANCH LINE TO THE GENERATOR IS NOT SHOWN.
 B) PLEASE SHOW THE 2 PSI DELIVERY PRESSURE AT THE
 METER. C) SHOW THE LOCATIONS OF THE LOW-PRESSURE
 REGULATORS. D) PLEASE PROVIDE THE PRINTED NAME AND
 SIGNATURE OF THE PERSON WHO PREPARED THE DRAWING- SEC.
 107.2.1 WPB.
  
 2) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE GENERATOR- SEC. 107.2.1 WPB.
 COMPLETE PLANS AND SPECIFICATIONS SHALL BE SUBMITTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  