Plan Review Notes
Plan Review Notes For Permit 21110486
Permit Number 21110486
Review Stop G
Sequence Number 2
Notes
Date Text
2022-01-13 15:50:122ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21110486
 1/13/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW. THE REQUESTED RISER
 DRAWING WAS NOT SUBMITTED. PLEASE NOTE A RISER DRAWING
 IS ALSO REFERRED TO AS AN ISOMETRIC DRAWING.
  
 1) FAILED. WPB AMENDMENTS TO FBC- SECTION 107.3.5.3:
 PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES ALL
 NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 3) FAILED. PLACE NOTES OR MEASUREMENTS ON THE PLAN TO
 INDICATE THE WATER HEATER WILL BE INSTALLED WITH
 REQUIRED CLEARANCES AS SPECIFIED BY THE MANUFACTURER
 AND IN ACCORDANCE WITH SECTION G2427.8 FBC RES. NOT
 PROVIDED.
  
 4) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SECTION- G2407.1 FBC RES. NOT PROVIDED.
  
 5) FAILED. SHOW THE LOCATION OF THE DRYER AND PROVIDE
 VENTING AND MAKEUP AIR DETAILS- SECTION G2439.1,
 G2439.3, & G2439.5 FBC RES. PLEASE SEE PAGE 16 OF THE
 SUBMITTED DRYER INSTALLATION INSTRUCTIONS. PROVIDE
 EITHER A LOUVERED DOOR OR MAKEUP AIR OPENING IN THE
 DOOR WITH A MINIMUM OF 100 SQ. INCHES.
 NEW COMMENT.
  
 1) THE SUBMITTED GAS PIPING TABLES ARE OUTDATED. IF
 SUBMITTING PIPE SIZING TABLES PLEASE SUBMIT THE CURRENT
 TABLES FOUND IN THE FBC-2020 RES. OR THE FBC-2020 FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  