2021-12-09 15:32:151ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110480
 12/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1.1 & A3.2: FBC ACC COMPLIANCE DETAILS
 REQUIRED:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SINK AND APPLIANCES- SECTION 606.2.
 B) HEIGHT OF THE SINK RIM OR COUNTER SURFACE FROM THE
 FINISHED FLOOR- SECTION 606.3.
 C) OPERABLE PARTS COMPLIANCE FOR APPLIANCES- 804.6.2.
 D) PLACE A NOTE TO INDICATE THE REFRIGERATOR/FREEZER
 SHALL HAVE AT LEAST 50 PERCENT OF THE FREEZER SPACE 54
 INCHES MAXIMUM ABOVE THE FINISH FLOOR- 804.6.6.
  
 2) P1.1, P3.1, & P4.2: PLEASE SHOW THE LOCATIONS OF THE
 REQUIRED CHECK VALVE AND FULL OPEN VALVE ON THE
 DISCHARGE PIPE AND VERIFY ACCESS WILL BD PROVIDED TO
 THE VALVES- SECTION 712.2 FBC P.
  
 3) P1.1, P3.1, & P4.2: INDICATE THE SUMP PIT WILL NOT
 BE LESS THAN 18 INCHES IN DIAMETER AND 24 INCHES IN
 DEPTH, WILL BE OF APPROVED MATERIALS, WILL HAVE A
 GAS-TIGHT REMOVABLE COVER- 712.3.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  