| 2022-02-08 09:29:08 | ELECTRIC REVIEW FAILED |
| | 1) ELECTRIC RISER STILL DETAILS INCORRECT WIRE SIZES |
| | AND GROUNDING ELECTRODE SYSTEM NEC 215.5 |
| | 2) PLANS INCORRECTLY DETAIL TWO PANELS SCHEDULES |
| | LABELED ?B? NEC 215.5 |
| | 3) PANEL ?B? IS NOT LABELED ON PLAN NEC 215.5 |
| | 4) METER IS NOT SHOWN ON PLANS NEC 215.5 |
| | 5) GROUNDING ELECTRODE SYSTEM IS INCORRECTLY DETAILED |
| | NEC 250.24 AND NEC 250.32 |
| | 6) GARAGE PLANS INCORRECTLY INDICATE SMOKE ALARMS, |
| | COMBINATION SMOKE CARBON MONOXIDE ALARMS ARE REQUIRED |
| | FBC R315.1 |
| | 7) SCOPE OF WORK DETAILED ON SHEET ?A2? DETAILS SCOPE |
| | AS ?REPLACE ALL ELECTRIC AND A/C ?. SHEET ?A5? DETAILS |
| | EXISTING ELECTRIC . PLEASE CORRECT FBC 107.2 |
| | 8) SHEET ?A5? STILL DOES NOT INDICATE SMOKE ALARMS AS |
| | REQUIRED. FBC 553.883 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |