2022-02-08 09:29:08ELECTRIC REVIEW FAILED
 1) ELECTRIC RISER STILL DETAILS INCORRECT WIRE SIZES
 AND GROUNDING ELECTRODE SYSTEM NEC 215.5
 2) PLANS INCORRECTLY DETAIL TWO PANELS SCHEDULES
 LABELED ?B? NEC 215.5
 3) PANEL ?B? IS NOT LABELED ON PLAN NEC 215.5
 4) METER IS NOT SHOWN ON PLANS NEC 215.5
 5) GROUNDING ELECTRODE SYSTEM IS INCORRECTLY DETAILED
 NEC 250.24 AND NEC 250.32
 6) GARAGE PLANS INCORRECTLY INDICATE SMOKE ALARMS,
 COMBINATION SMOKE CARBON MONOXIDE ALARMS ARE REQUIRED
 FBC R315.1
 7) SCOPE OF WORK DETAILED ON SHEET ?A2? DETAILS SCOPE
 AS ?REPLACE ALL ELECTRIC AND A/C ?. SHEET ?A5? DETAILS
 EXISTING ELECTRIC . PLEASE CORRECT FBC 107.2
 8) SHEET ?A5? STILL DOES NOT INDICATE SMOKE ALARMS AS
 REQUIRED. FBC 553.883
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  