| Plan Review Notes For Permit 21110475 |
| Permit Number |
21110475 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-14 15:51:11 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NO SMOKE ALARMS SHOWN PER FBC R314, 315 | | | | | | RISER IS SHOWING A 300A PANEL WITH 2/0S 100A PANEL WITH | | | 2/0S PLEASE SUBMIT A WHOLE SERVICE LOAD CALCULATION FOR | | | THE 300A METER. 215.5 | | | | | | PANELS ARE SHOWN AS MLO OCP REQUIRED AT SERVICE TO BE | | | GROUPED PER 230.72 |
|