2021-11-14 15:51:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO SMOKE ALARMS SHOWN PER FBC R314, 315
  
 RISER IS SHOWING A 300A PANEL WITH 2/0S 100A PANEL WITH
 2/0S PLEASE SUBMIT A WHOLE SERVICE LOAD CALCULATION FOR
 THE 300A METER. 215.5
  
 PANELS ARE SHOWN AS MLO OCP REQUIRED AT SERVICE TO BE
 GROUPED PER 230.72