| Plan Review Notes For Permit 21110473 |
| Permit Number |
21110473 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-02-01 16:42:43 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B/WPB AMENDMENTS 107.2.1, PLEASE SUBMIT A NEW FLOOR | | | PLAN WITH THE CORRECTION OF THE BUILDING MEAN ROOF | | | HEIGHT (240') AND PLEASE HAVE SUBMITTAL SIGNED BY | | | PERSON RESPONSIBLE (POSSIBLY THE CONTRACTOR). | | | | | | NOTE: A PROVISO WAS ADDED TO THE SLIDING GLASS DOOR | | | PRODUCT APPROVAL(FL27914 R2) FOR THE REQUIRED SILL | | | HEIGHT OF 3.375". |
|