| 2021-11-24 10:18:03 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21110473 |
| | ADD: 2450 PRESIDENTIAL WAY # 1908 |
| | PCN:74-43-43-18-10-000-1908 |
| | CONT: WRIGHT?S IMPACT WINDOW & DOOR LLC |
| | TEL: 561-588-7353 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. NOV. 24TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) THE WRIGHT?S FLOOR PLAN & OPENING SCHEDULE NEEDS TO |
| | SHOW WHO THE AUTHOR IS OF THE PLAN. CERTIFICATION BY |
| | CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT |
| | CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY |
| | THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT |
| | YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE |
| | TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | |
| | 2A) DRAWING 1 WRIGHT?S FLOOR PLAN DOES NOT SHOW THE |
| | FLOOR PLAN IN THE OVER ALL CURVATURE OF THE BUILDING, |
| | NOR THE UNITS THAT ARE PROJECTED FURTHER OUT THAN OTHER |
| | PORTIONS OF THE WALL LINE CREATING A FLUTTERING OR |
| | GALLOPING AFFECT. THE ENGINEERING SHEET STATES THE |
| | MINIMUM BUILDING WIDTH OF 50 FEET. ASSUMED VALUE FOR |
| | END ZONE WIDTH FROM A CORNER IS 5 FEET. PLEASE PROVIDE |
| | THE DISTANCE AWAY FROM THE CORNER FOR WINDOW IDENTIFIED |
| | AS NUMBER 9. |
| | |
| | 2B) ENGINEERING EXPRESS SHEET SHOWS FOR COMPLEX |
| | BUILDINGS USE CORNER ZONES IF AT ALL IN QUESTION. THIS |
| | WILL GREATLY AFFECT THE PRESSURES ON THESE OPENINGS AND |
| | SUBMITTED SCHEDULE. |
| | BUILDING END ZONES (5). THE FLOOR PLAN LAYOUT INDICATES |
| | THE WORK TO BE PERFORMED UNDER THIS PERMIT IS A CORNER |
| | UNIT OF A HIGHRISE BUILDING. THE WIND LOAD CHART UNDER |
| | NOTES STATES WHAT IS CONSIDERED AN END ZONE 10% OF THE |
| | LEAST HORIZONTAL DISTANCE OF THE BUILDING OR 40% OF THE |
| | MRH, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL |
| | DISTANCE OR 3 FT. THE CONTRACTOR HAS NOT IDENTIFIED |
| | WHAT THE LEAST HORIZONTAL DISTANCE IS FOR THE BUILDING |
| | NOR THE LOCATION OF THE UNIT IN RELATIONSHIP TO THE |
| | BUILDING AND THE INTERCOASTAL WATERWAY. EXAMPLE ONLY. |
| | IF THE BUILDING HEIGHT IS APPROXIMATELY 180 FT. (MRH.) |
| | X 0.40= 72 FEET. THIS WOULD PUT ALL OPENINGS IN WIND |
| | ZONE 5 OR 10% OF THE LEAST HORIZONTAL DISTANCE OF THE |
| | BUILDING, ALSO UNKNOWN. |
| | |
| | 2B) THE OTHER UNKNOWN IS THE BUILDING HEIGHT DEPENDING |
| | ON THE PERMIT: |
| | 21110473/ 2450 PRESIDENTIAL WAY # 1908 200? |
| | 21110246/ 2450 PRESIDENTIAL WAY # 1707 240? |
| | 21110466/ 2450 PRESIDENTIAL WAY # 807 240? |
| | 21101014/ 2480 PRESIDENTIAL WAY # 501 220? |
| | 2110470/ 2450 PRESIDENTIAL WAY #1207 200? |
| | 21110245/ 2480 PRESIDENTIAL WAY # 1104 200? |
| | 21110469/ 2450 PRESIDENTIAL WAY # 206 190? |
| | |
| | |
| | 3) THE REVIEW OF THE SUBMITTED PRODUCT APPROVALS CANNOT |
| | OCCUR WITH ALL THE UNKNOWNS LISTED IN COMMENT 2. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |