| 2022-01-19 09:18:54 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21110470 |
| | ADD: 2450 PRESIDENTIAL WAY # 1207 |
| | PCN:74-43-43-18-10-000-1207 |
| | CONT: WRIGHTS IMPACT WINDOW & DOOR LLC |
| | TEL: 561-588-7353 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: WED. JAN. 19TH/ 2022 |
| | ACTION: DENIED |
| | |
| | ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA |
| | STATUTE 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1-2) COMPLIED. |
| | |
| | 3) 3RD REQUEST. THE SLIDING GLASS NOA 21-0728.02 |
| | REVISION C PAGE 5 OF 23 IS NOT THE CURRENT VERSION OF |
| | THE PRODUCT APPROVAL SEE MIAMI-DADE WEB-SITE, MISSING |
| | SILL HEIGHTS THE NEW REVISION D DOES SHOW SILL HEIGHTS |
| | AND THE SILL HEIGHTS AND ASSOCIATED PRESSURES ARE THE |
| | LIMITING FACTOR FOR POSITIVE PRESSURES. CIRCLE IDENTIFY |
| | WHICH SILL HEIGHT IS TO BE INSTALLED FOR THIS |
| | APPLICATION. |
| | |
| | 2ND REQUEST. THE REVIEW OF THE SUBMITTED PRODUCT |
| | APPROVAL NOA 21-0728.02 REVISION C, SLIDING GLASS DOORS |
| | CANNOT BE DETERMINED BUT ALREADY THERE ARE ISSUES WITH |
| | THE SILLS, THE POSITIVE AND NEGATIVE PRESSURES ARE |
| | GIVEN ON PAGE 5 OF 23, PAGE 14OF 23 SHOWS A 3 11/16 |
| | INCH SILL NO PRESSURES GIVEN AND PAGE 21 OF 23 SHOWS 2 |
| | INCH SILLS. I DO NOT SEE WHERE THERE ARE POSITIVE |
| | PRESSURES GIVEN FOR THE SILLS. YOU ARE NOT USING THE |
| | CURRENT VERSION OF THIS PRODUCT APPROVAL. ON MIAMI-DADE |
| | WEBSITE NOA 21-0728.02 REVISION D 08/04/21 PAGE 5/23 |
| | TECHNICAL DRAWINGS SHOWS SILL HEIGHTS AND ASSOCIATED |
| | PRESSURES. UPDATE YOUR NOA TO THE NEWEST VERSION AND |
| | CIRCLE WHICH SILL HEIGHT TO BE INSTALLED. THE 2 INCH |
| | SILL DOES NOT MEET THE REQUIRED POSITIVE PRESSURES OF |
| | ZONE 4. WITH THE HIGHER POSITIVE PRESSURES OF ZONE 5THE |
| | 3 1/8-INCH SILL MAY NOT WORK. ZONE 5 THE NEGATIVE |
| | PRESSURES WILL ALSO INCREASE. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |