| 2021-11-29 08:33:03 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) IT APPEARS THAT YOU INTEND TO REPLACE ALL OF THE |
| | PLUMBING IN A TWO STORY (4) UNIT APARTMENT BUILDING |
| | THAT WAS CONSTRUCTED IN 1930. THIS WORK WILL REQUIRE |
| | THE WALLS, FLOORS AND CEILINGS TO BE OPENED FOR ACCESS |
| | TO REPLACE THE EXISTING PLUMBING. THE TENANT SEPARATION |
| | WALLS BETWEEN THE UNITS ARE REQUIRED TO HAVE A ONE HOUR |
| | FIRE RESISTIVE RATING. A BUILDING CONTRACTOR IS |
| | REQUIRED TO OBTAIN A PERMIT TO COMPLETE THIS WORK. FBC |
| | AMENDMENTS 105.1 |
| | |
| | 2) PROVIDE A FULL SCOPE OF WORK. SPECIFY IF NEW |
| | FIXTURES, VANITIES AND KITCHEN CABINETS WILL BE |
| | INSTALLED. FBC AMENDMENTS 107.2.1 |
| | |
| | 3) PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR |
| | PLAN. FBC AMENDMENTS 107.2 |
| | |
| | 4) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS PER THE |
| | FBC EXISTING BUILDING CHAPTER 6. |
| | |
| | 5) PROVIDE DETAILS FOR THE ONE HOUR FIRE RESISTANCE |
| | RATED TENANT SEPARATION WALLS AND FOR THE PROTECTION OF |
| | OPENINGS OR PENETRATIONS IN THESE WALLS. FBC 714 |
| | |
| | 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. PLEASE NOTE |
| | THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS |
| | MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |