| Plan Review Notes For Permit 21110446 |
| Permit Number |
21110446 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-29 11:56:17 | 11/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM | | | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) | | | RESIDENTIAL PLUMBING. | | | | | | 2. THE MASTER BATHROOM IS NOT VENTING THE TUBS | | | CORRECTLY AND THE BATHROOM GROUP NEED TO BE SEPARATE | | | FROM THE BUILDING DRAIN CATCHING OTHER FIXTURES UP | | | STREAM PER THE 2020 FBC SEC. R P3101.2.1 VENTING | | | REQUIRED AND P 3108.2.1HORIZONTAL WET VENT. | | | | | | 3. WOULD YOU PLEASE SHOW LOCATION OF THE NEW WATER | | | HEATER PER THE WPB AMEND TO FBC 107.2.1 | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | | | | | | | |
|