| 2021-11-19 07:11:25 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21110446 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS FOR THE |
| | NEWLY CONDITIONED GUEST HOUSE. FBC EC R402.1 |
| | |
| | 2) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEWLY |
| | CONDITIONED GUEST HOUSE. FBC EC R403.7 |
| | |
| | 3) PLEASE PROVIDE ANCHORAGE DETAILS FOR THE CONDENSING |
| | UNIT FOR THE GUEST HOUSE. FBC RES M1307.2 |
| | |
| | 4) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEW |
| | ADDITION. FBC EC R402.1 |
| | |
| | 5) PLEASE PROVIDE THE MECHANICAL SIZING CALCULATIONS |
| | FOR THE NEW ADDITION. FBC EC R403.7 |
| | |
| | 6) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE |
| | MECHANICAL SYSTEM AND DUCTWORK FOR THE NEW ADDITION. |
| | FBC 107.2.1 |
| | |
| | 7) PLEASE PROVIDE INFORMATION ON THE KITCHEN HOOD, CFM |
| | OF EXHAUST, MAKE UP AIR REQUIRED? FBC RES M1503.1 |
| | |
| | 8) PLEASE SHOW THE DRYER DUCT AND TERMINATION LOCATION. |
| | FBC RES M1502 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |