| Date |
Text |
| 2021-12-22 08:02:55 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21110389 |
| | ADD: 2450 PRESIDENTIAL WAY # 607 |
| | CONT: J & M CONTRACTORS OF S FLORIDA |
| | TEL: 561-718-7040 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 22/2021 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1: |
| | 1A) THE HEADING OF EXISTING BUILDING CODE LIST THE |
| | LEVEL OF ALTERATION AS LEVEL 1. PLEASE NOTE IN THE |
| | BEDROOM # 2 BATH THERE IS THE RECONFIGURATION OF SPACE |
| | WITH THE REMOVAL OF THE TUB FOR NEW SHOWER, CURB, TILE |
| | DRAIN COVER AND VALVE. RECONFIGURE OF SPACE BATH# 2 |
| | REMOVE SWING DOOR AND RECONFIGURE TO POCKET DOOR. |
| | LAUNDRY REMOVAL OF SINK. |
| | LEVEL 2 ALTERANITIONS, 2020 EXIST. BUILD. CODE. SECTION |
| | 603. LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF |
| | SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR |
| | WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, |
| | OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. |
| | |
| | 1B) THE FLOOR PLAN INDICATES IN SHOWERS THE REMOVAL OF |
| | WALL TILE BUT THERE IS NO REFERENCE TO THE TYPE OF |
| | BACKER BOARD TO BE INSTALLED. PLEASE SHOW COMPLIANCE |
| | WITH 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS |
| | A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| | AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| | RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| | FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| | THE MANUFACTURE?S RECOMMENDATIONS. |
| | |
| | 1C) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| | COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| | SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| | HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| | |
| | 1D) THE PLAN SHOWS LIGHT FIXTURES IN THE LIVING ROOM |
| | CEILING BUT THERE IS NO MENTION OF THIS IS AN EXISTING |
| | DROPPED CEILING? IF NOT PLEASE PROVIDE A FRAMING |
| | DETAIL, TYPE OF FRAMING, GAUGE, SPACING AND ANCHORING |
| | TO THE CONCRETE DECK ABOVE, TYPE OF FINISH MATERIAL AND |
| | THICKNESS. 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 1E) THE LIVING ROOM FLOOR PLAN ALSO INDICATES TO ADD A |
| | 2 INCH DROP CEILING THIS ROOM ONLY, IS THIS A DROP 2 |
| | INCHES LOWER THAT THE EXISTING CEILING OR A 2 INCH |
| | DROPPED SOFFIT? 107.2.1.2. ADDITIONAL INFORMATION |
| | REQUIRED, CLARIFICATION. |
| | |
| | 1F) PROJECT CODE REFERENCES: THE 2020 FBC-RESIDENTIAL |
| | CODE, PLEASE NOTE THE RESIDENTIAL CODE IS FOR ONE & TWO |
| | FAMILY DWELLINGS (R-3 OCCUPANCIES). THE CODE REFERENCE |
| | SHOULD BE THE 2020 FBC-BUILDING CODE FOR (R2 |
| | OCCUPANCIES, CONDOMINIUMS & APARTMENTS). |
| | |
| | 1G) THERE ARE THREE FLOORING NOTES: |
| | 1G)(1) NEW FLOORING THROUGHOUT EXCEPT FOR THE MASTER |
| | BATHROOM. |
| | 1G)(2)FLOORING REQUIREMENTS. SECTION 1207.3 STRUCTURE |
| | BORNE SOUND. SOUND PROOFING: SUPER SAM 125 TO |
| | BE INSTALLED UNDER NEW MARBLE. |
| | 1G)(3) TYPICAL INTERIOR METAL WALL SECTION. CONCRETE |
| | FLOORS ADD VINYL/ TILE/CARPET PER OWNER |
| | WHICH ONES DO WE USE, CLARIFY PLEASE? NOTE WE WILL |
| | UPLOAD REPORTS FOR SUPER SAM 125 FOR MARBLE AND TILE IF |
| | THIS IS THE CHOICE OF FINISH FLOOR MATERIAL. |
| | |
| | 2) CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF |
| | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| | PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |