2022-02-14 14:57:392ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110363
 2/14/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAP LETTERS.
  
 5) FAILED. CS-1 & P1: REFER TO TABLE 403.1 FBC P AND
 PROVIDE PLUMBING FIXTURE CALCULATIONS FOR THE NEW
 RESTROOM BUILDING. PROVIDE A SCHEDULE INDICATING THE
 REQUIRED AND PROVIDED NUMBER OF FIXTURES. REFER TO SEC.
 211.2 FBC ACC- NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 (WHEELCHAIR ACCESSIBLE) AND
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7 (STANDING
 PERSONS) FBC ACC. THE PLUMBING FIXTURE CALCULATIONS
 WERE NOT PROVIDED. PLEASE NOTE THAT U OCCUPANCY
 CLASSIFICATIONS (SEE SEC. 312.1 FBC B) ARE NOT INCLUDED
 IN TABLE 403.1 FBC P. HOW WERE THE NUMBER OF FIXTURES
 FOR THE RESTROOM DETERMINED? PLEASE NOTE THAT SERVICE
 SINKS FOR BUILDING SANITATION ARE REQUIRED FIXTURES FOR
 MOST USES AND OCCUPANCIES.
  
 7) FAILED A, B, C, D, E. A1: ADDITIONAL DETAILS
 REQUIRED IN ACCORDANCE WITH THE FBC- 2020 ACCESSIBILITY
 CODE.
 A) FAILED. SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE WATER CLOSETS- SEC. 604.3.
 DIMENSIONS NOT PROVIDED
 B) FAILED. SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE LAVATORIES- 606.2. DIMENSIONS NOT
 PROVIDED
 C) FAILED. SHOW THE TURNING SPACE DIAMETERS- 304.3.
 DIAMETER NOT PROVIDED
 D) FAILED. SHOW THE HEIGHTS OF THE MIRRORS FROM THE
 FINISHED FLOORS TO THE REFLECTIVE SURFACES- 603.3. SHOW
 THE MEASUREMENT TO THE REFLECTIVE SURFACE.
 E) FAILED. SHOW THE MINIMUM LENGTHS, AND MOUNTING
 HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS- 604.5 &
 609.4, AS DEPICTED IN FIGURES 604.5.1 & 604.5.2. THE
 CURRENT DETAILS DO NOT SHOW THE MINIMUM 54-INCH SIDE
 BAR EXTENSION FROM THE REAR WALL, AND THE MOUNTING
 HEIGHTS TO THE TOPS OF THE GRAB BAR GRIPPING SURFACES.
 SHOW THE GRAB BAR EXTENSION ON THE SIDEWALL TO BE
 MINIMUM 54-INCHES. SHOW THE HEIGHTS OF THE GRAB BARS TO
 THE TOPS OF THE GRIPPING SURFACES.
  
 9) FAILED B. A2: ROOF DRAINAGE:
 A) REFER TO SEC. 1106.1 FBC P AND PROVIDE ROOF DRAINAGE
 CALCULATIONS BASED ON THE RATE- SECS. 1106.1- 1106.4
 FBC P.
 B) FAILED A1 & A2. PLEASE SEE TABLES 1106.3 & 1106.6
 FBC P AND PROVIDE GUTTER AND DOWNSPOUT SIZES. PLEASE
 SEE TABLES 1106.3 & 1106.6 FBC P AND PROVIDE THE GPM
 CAPACITIES OF THE GUTTERS AND DOWNSPOUTS IN ORDER TO
 VERIFY SIZES ARE CODE COMPLIANT.
  
 NEW COMMENT
  
 1) REFER TO SECS. 403.3.3 & 403.5 FBC P AND VERIFY THE
 LOCATIONS OF THE RESTROOM FIXTURES AND DRINKING
 FOUNTAINS DO NOT EXCEED A TRAVEL DISTANCE OF 500 FT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719