2021-12-21 10:45:121ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110363
 12/21/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: REFERENCES ARE MADE TO CIVIL DRAWING WHICH
 HAVE NOT BEEN PROVIDED. PLEASE SUBMIT THE DRAWINGS
 INCLUDING WATER/SEWER AND DRAINAGE PLANS. THE
 WATER/SEWER SHALL SHOW LOCATIONS OF WATER MAIN, POINT
 OF WATER SERVICE CONNECTION, METER AND BACKFLOW
 LOCATION, SEWER/BUILDING DRAIN POINT OF CONNECTION, AND
 LOCATION OF THE SEPTIC TANK. THE DRAINAGE PLANS SHALL
 SHOW STORM DRAIN LATERAL AND BUILDING STORM DRAIN
 POINTS OF CONNECTION, AND/OR LOCATIONS OF ROOF DRAINAGE
 AREAS, AND CATCH BASINS- SECS. 107.2.1, 110.9 WPB AND
 SEC. 1101.2 FBC P. PLEASE NOTE INSTALLATION OF THE
 SEPTIC TANK SHALL BE COMPLIANCE WITH FAC RULE 64E-6 AND
 A PERMIT MUST BE OBTAINED FROM THE PB COUNTY DEPARTMENT
 OF HEALTH. OTHER REQUIRED SEPARATE PERMITS ARE:
 A) POTABLE WATER SERVICE BACKFLOW PREVENTER.
 B) IRRIGATION.
 C) IRRIGATION SERVICE BACKFLOW PREVENTER.
 PLEASE NOTE THAT FL. LICENSED PLUMBING CONTRACTORS
 SHALL OBTAIN SEPARATE PERMITS FOR INSTALLATION OF THE
 BACKFLOW PREVENTERS IN ACCORDANCE WITH SECTION 105.1
 WPB AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE
 SHALL BE TESTED AND CERTIFIED BY THE WPB UTILITIES
 DEPARTMENT PRIOR TO FINAL INSPECTION BY THE BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT.AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 2) P1: SHOW THE WATER SUPPLY CONNECTION TO THE ICE
 MAKER AND LOCATIONS OF THE WATER HAMMER ARRESTOR AND
 BACKFLOW PREVENTER- SECS. 604.9 & 608.3 FBC P.
  
 3) P1: PLEASE INCLUDE THE FLOOR SINK, FLOOR DRAIN, AND
 ICE MAKER IN THE FIXTURE SCHEDULE- SECS. 413 & 414 FBC
 P.
  
 4) P1: PROVIDE TRAP SEAL PROTECTION FOR THE EMERGENCY
 FLOOR DRAINS- SEC. 1002.4.1 FBC P.
  
 5) CS-1 & P1: REFER TO TABLE 403.1 FBC P AND PROVIDE
 PLUMBING FIXTURE CALCULATIONS FOR THE NEW RESTROOM
 BUILDING. PROVIDE A SCHEDULE INDICATING THE REQUIRED
 AND PROVIDED NUMBER OF FIXTURES. REFER TO SEC. 211.2
 FBC ACC- NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 (WHEELCHAIR ACCESSIBLE) AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7 (STANDING PERSONS) FBC
 ACC.
  
 6) A1 & P1: PLEASE LABEL THE TOILET ROOMS AS EITHER
 MALE OR FEMALE- SEC. 403.2 FBC P AND INDICATE WHICH
 GROUPS OF PEOPLE WILL BE USING THE FACILITIES- THE
 PUBLIC, EMPLOYEES, BOTH GROUPS?- SEC. 403.3.
  
 7) A1: ADDITIONAL DETAILS REQUIRED IN ACCORDANCE WITH
 THE FBC- 2020 ACCESSIBILITY CODE.
 A) SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE WATER CLOSETS- SEC. 604.3.
 B) SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- 606.2.
 C) SHOW THE TURNING SPACE DIAMETERS- 304.3.
 D) SHOW THE HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- 603.3
 E) SHOW THE MINIMUM LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- 604.5 & 609.4, AS
 DEPICTED IN FIGURES 604.5.1 & 604.5.2. THE CURRENT
 DETAILS DO NOT SHOW THE MINIMUM 54-INCH SIDE BAR
 EXTENSION FROM THE REAR WALL, AND THE MOUNTING HEIGHTS
 TO THE TOPS OF THE GRAB BAR GRIPPING SURFACES.
 F) SHOW MAX 48-INCH REACH HEIGHTS FOR PAPER DISPENSERS
 AND CONTROL HANDLES- SEC. 308.
 G) DRINKING FOUNTAINS: REFER TO SECS. 306, 307, AND 602
 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW
 THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SEC. 602.2
 FBC ACC AND SHOW HOW THE LOCATIONS OF THE FOUNTAINS
 WILL BE IN COMPLIANCE WITH SECTION 307.2 PROTRUSION
 LIMITS.
  
 8) A1: SHOW THE CLEAR FLOOR SPACE APPROACH DIAGRAM FOR
 THE ICE MACHINE AND REACH RANGE TO THE CONTROLS. VERIFY
 OPERABLE CONTROL COMPLIANCE. VERIFY COMPLIANCE FOR
 REACH RANGE AND OPERABLE CONTROL- SECS. 904.5.1, 308 &
 309 FBC ACC.
  
 9) A2: ROOF DRAINAGE:
 A) REFER TO SEC. 1106.1 FBC P AND PROVIDE ROOF DRAINAGE
 CALCULATIONS BASED ON THE RATE- SECS. 1106.1- 1106.4
 FBC P.
 B) PLEASE SEE TABLES 1106.3 & 1106.6 FBC P AND PROVIDE
 GUTTER AND DOWNSPOUT SIZES.
 C) SHOW THE DOWNSPOUT DISCHARGE LOCATIONS. CLARIFY IF
 THE DOWNSPOUTS WILL CONNECT TO AN UNDERGROUND STORM
 DRAIN SYSTEM OR BE DISCHARGED TO GRADE. REFER TO
 COMMENT #1 AND PROVIDE CIVIL DRAWINGS SHOWING STORM
 DRAINAGE POINTS OF CONNECTIONS (IF APPLICABLE), OR
 REFER TO SEC. 1503.7 FBC B AND INDICATE THE DOWNSPOUTS
 WILL DISCHARGE AT LEAST 1 FOOT AWAY FROM THE BUILDING
 SIDE WALL TO APPROVED LOCATIONS OF DISPOSAL- SEC.
 1101.2 FBC P.
  
 10) FLOOD HAZARD: FOR STRUCTURES LOCATED IN FLOOD
 HAZARD AREAS, THE FOLLOWING SYSTEMS AND EQUIPMENT SHALL
 BE LOCATED AND INSTALLED AS REQUIRED BY SECTION 1612 OF
 THE FLORIDA BUILDING CODE, BUILDING, AND ASCE 24-14.
  
 1. WATER SERVICE PIPES.
 2. PUMP SEALS IN INDIVIDUAL WATER SUPPLY SYSTEMS WHERE
 THE PUMP IS LOCATED BELOW THE DESIGN FLOOD ELEVATION.
 3.COVERS ON POTABLE WATER WELLS SHALL BE SEALED, EXCEPT
 WHERE THE TOP OF THE CASING WELL OR PIPE SLEEVE IS
 ELEVATED TO NOT LESS THAN 1 FOOT (305 MM) ABOVE THE
 DESIGN FLOOD ELEVATION.
 4.SANITARY DRAINAGE PIPING.
 5.STORM DRAINAGE PIPING.
 6.MANHOLE COVERS SHALL BE SEALED, EXCEPT WHERE ELEVATED
 TO OR ABOVE THE DESIGN FLOOD ELEVATION.
 7.OTHER PLUMBING FIXTURES, FAUCETS, FIXTURE FITTINGS,
 PIPING SYSTEMS AND EQUIPMENT.
 8.WATER HEATERS.
 9.VENTS AND VENT SYSTEMS.
  
 EXCEPTION: THE SYSTEMS LISTED IN THIS SECTION ARE
 PERMITTED TO BE LOCATED BELOW THE ELEVATION REQUIRED BY
 SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING FOR
 UTILITIES AND ATTENDANT EQUIPMENT, PROVIDED THAT THE
 SYSTEMS ARE DESIGNED AND INSTALLED TO PREVENT WATER
 FROM ENTERING OR ACCUMULATING WITHIN THEIR COMPONENTS
 AND THE SYSTEMS ARE CONSTRUCTED TO RESIST HYDROSTATIC
 AND HYDRODYNAMIC LOADS AND STRESSES, INCLUDING THE
 EFFECTS OF BUOYANCY, DURING THE OCCURRENCE OF FLOODING
 UP TO SUCH ELEVATION.
  
 10A) PLEASE REVIEW ASCE 24-14 SEC. 7.3 PLUMBING SYSTEMS
 RELATING TO SYSTEMS IN FLOOD HAZARDS ZONES:
  
 SECTION 7.3.1: THE PLUMBING PIPES SHALL BE BURIED TO A
 DEPTH SUFFICIENT TO PREVENT MOVEMENT, SEPARATION, OR
 LOSS DUE TO FLOODING AND EROSION UNDER DESIGN FLOOD
 CONDITIONS.
 7.3.2: THE PLUMBING PIPING EMERGING FROM UNDERGROUND
 SHALL BE DESIGNED, CONSTRUCTED, ANCHORED, AND PROTECTED
 TO WITHSTAND FLOOD-RELATED LOADS, INCLUDING THE EFFECTS
 OF BUOYANCY, HYDRODYNAMIC FORCES, AND DEBRIS IMPACT.
 7.3.3: THE PLUMBING SYSTEM AND COMPONENTS SHALL BE
 ELEVATED AT A MINIMUM OF 2 FT. ABOVE THE BFE + 2 FT. OR
 THE DFE WHICHEVER IS HIGHER PER TABLE 7-1. OPENINGS
 BELOW THE REQUIRED ELEVATION SHALL BE PROTECTED WITH
 AUTOMATIC BACKWATER VALVES OR OTHER AUTOMATIC BACKFLOW
 DEVICES. DEVICES SHALL BE INSTALLED IN EACH LINE THAT
 EXTENDS BELOW THE DFE TO PREVENT RELEASE OF SEWAGE INTO
 FLOODWATERS AND TO PREVENT INFILTRATION BY FLOODWATERS
 INTO THE PLUMBING.
 7.3.4: SANITARY SYSTEM STORAGE TANKS SHALL BE DESIGNED,
 CONSTRUCTED, INSTALLED, AND ANCHORED TO RESIST AT LEAST
 1.5 TIMES THE POTENTIAL BUOYANT AND OTHER FLOOD FORCES
 ACTING ON AN EMPTY TANK DURING DESIGN FLOOD CONDITIONS.
 TANKS AND PIPING SHALL BE INSTALLED TO RESIST LOCAL
 SCOUR AND EROSION.
  
 11) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUALS FOR ALL FIXTURES, APPLIANCES, EQUIPMENT, AND
 DEVICES SHALL BE REVIEWED AND APPROVED BY THE
 RESPONSIBLE DESIGN PROFESSIONAL IN CHARGE AND SUBMITTED
 FOR REVIEW. IF THE SUBMITTALS ARE TO BE DEFERRED PLEASE
 PROVIDE A LIST ON THE PLANS- SEC. 107.3.4.1 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER