Plan Review Notes
Plan Review Notes For Permit 21110362
Permit Number 21110362
Review Stop P
Sequence Number 2
Notes
Date Text
2022-02-14 12:56:572ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110362
 2/14/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAP LETTERS.
  
 1) FAILED. SHEET P2 NOTES 1 & 2: REFERENCE IS MADE TO
 SHEET P1. PLEASE SUBMIT THE SHEET- SEC. 107.2.1 WPB.
 ACCORDING TO THE ARCHITECT?S RESPONSE NARRATIVE P1 WAS
 UPLOADED, HOWEVER IT WAS NOT. DOES SHEET P1 EXIST OR IS
 THE PLAN LABEL A TYPO BY THE ARCHITECT?
  
 3) FAILED. A1.01, P2 & P3: REFER TO SECS. 803.1 & 803.2
 FBC P AND PROVIDE AN APPROVED CHEMICAL DILUTION OR
 NEUTRALIZING DEVICE AND SYSTEM FOR THE MIX/LOAD. REFER
 TO COMMENT #10 FOR FURTHER INFORMATION. PRODUCT DATA
 SHEETS FOR THE MODEL 1500 AND GSMS HAVE BEEN SUBMITTED,
 HOWEVER THEIR LOCATIONS ON THE PLANS ARE NOT CLEAR. IT
 APPEARS KEYNOTE 11 IDENTIFIES THE GSMS. WHICH NOTE
 INDENTIFIES THE MODEL 1500?
  
 6) FAILED. BACKFLOW PREVENTION: IN ACCORDANCE WITH THE
 WEST PALM BEACH UTILITIES CROSS CONNECTION MANUAL
 AN RPZ BACKFLOW ASSEMBLY (REDUCED PRESSURE ZONE) SHALL
 BE INSTALLED ON THE POTABLE WATER SERVICE LINE. AS
 NOTED IN COMMENT #1 ABOVE, THE LOCATION OF THE RPZ
 SHALL BE SHOWN ON THE CIVIL PLANS AND MANUFACTURER'S
 SPECIFICATIONS SHALL BE SUBMITTED FOR REVIEW. THE CIVIL
 PLAN SHEET C3.4 SHOWS AN RPZ FOR THE POTABLE WATER
 SERVICE TO MAINTENANCE BUILDING A HOWEVER A BACKFLOW
 ASSEMBLY IS NOT PROVIDED FOR THE SERVICE TO BUILDING C.
 PLEASE CONTACT THE WPB UTILITIES DEPT. FOR FURTHER
 INFORMATION AT 561-822-2210.
 PLEASE NOTE THAT FL. LICENSED PLUMBING CONTRACTORS
 SHALL OBTAIN SEPARATE PERMITS FOR INSTALLATION OF THE
 BACKFLOW PREVENTERS IN ACCORDANCE WITH SECTION 105.1
 WPB AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICES
 SHALL BE TESTED AND CERTIFIED BY THE WPB UTILITIES
 DEPARTMENT PRIOR TO FINAL INSPECTION BY THE BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT.AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 7) FAILED. A1.01, P2, P3: PROVIDE THE USE AND OCCUPANCY
 CLASSIFICATION OF THE BUILDING, OCCUPANT LOAD, AND
 PLUMBING FIXTURE CALCULATIONS IN COMPLIANCE WITH TABLE
 403.1 FBC P. NOT PROVIDED OR INCLUDED ON THE LIFE
 SAFETY PLAN- LS1.01. PLEASE REVISE THE OCCUPANT LOAD
 AND FIXTURE CALCULATIONS TO INCLUDE ALL EMPLOYEES
 ASSOCIATED WITH BUILDINGS B & C- SEC. 403.3 FBC P.
  
 8) FAILED. P2 & P3: SHOW THE LOCATIONS OF THE POTABLE
 WATER BACKFLOW PREVENTER AND OIL SEPARATOR ON THE
 PLANS- SEC. 107.2.1 WPB. SEE COMMENT #6 ABOVE.
  
 9) FAILED P2 & P3: PROVIDE A SANITARY DRAIN AND VENT
 LAYOUT PLAN AND ISOMETRIC DRAWING- SECS 107.2.1 &
 107.3.5.1.3 WPB. NOT PROVIDED. THE PLANS DO NOT CLEARLY
 SHOW HOW THE DISCHARGES FROM THE CHEMICAL SINK AND
 EMERGENCY SHOWER/EYE WASH WILL BE CONVEYED TO THE
 SANITARY DRAINAGE SYSTEM- SECS. 301.3 & 701.2 FBC P.
 PLEASE NOTE NO DRAINS FOR THESE FIXTURES ARE SHOWN ON
 THE PLANS.
  
 10) FAILED A, B, C, & D. A1.01, P2 & P3: REFER TO SECS.
 803.1 & 803.2 FBC P AND PROVIDE AN APPROVED CHEMICAL
 DILUTION OR NEUTRALIZING DEVICE FOR THE CHEMICAL WASTE
 IN THE MIX/LOAD ROOM. PLEASE EXPLAIN THE PROCESSES THAT
 WILL OCCUR IN THE ROOM AND PROVIDE AN ENLARGED CHEMICAL
 DRAIN AND VENT PIPING SCHEMATIC OR ISOMETRIC DRAWING
 THAT INCLUDES THE DRAINAGE CONNECTION FROM THE SYSTEM
 TO AN APPROVED PLACE OF DISPOSAL- SEC. 803.2 FBC P &
 SEC. 107.2.1 WPB. THE ARCHITECT DID NOT RESPOND TO THIS
 COMMENT AND NO ADDITIONAL INFORMATION PROVIDED ON THE
 PLANS.
 A) FAILED REVISE SHEETS P2 & P3 TO SHOW THE CHEMICAL
 SYSTEM DRAINAGE SYSTEM PIPING LAYOUT- 107.3.5.1.3 WPB.
 NOT PROVIDED, NO RESPONSE.
 B) FAILED. REVISE SHEETS P2 & P3 TO SHOW THE POTABLE
 WATER PIPING CONNECTIONS TO ALL FIXTURES IN THE
 MIX/LOAD ROOM INCLUDING THE EMERGENCY EYEWASH STATION,
 CHEMICAL SINK, AND CLOSED LOOP WASH SYSTEM. SHOW THE
 LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS AND
 BACKFLOW PREVENTERS AND INCLUDE BACKFLOW SPECIFICATIONS
 AND LISTINGS- SECS. 604.5, 608.3 & TABLE 608.3 FBC P.
 THE SUBMITTAL FOR THE MODEL 1500 SHOWS A ?-INCH POTABLE
 WATER FEED IS REQUIRED. PLEASE SHOW THE LOCATION AND
 SUPPLY LINE ON P2 & P3. IT APPEARS ONLY THE LINE TO THE
 GSMS IS SHOWN.
 C) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 PIPING, FIXTURES AND EQUIPMENT IN THE MIX/LOAD AND
 FUELING STATION ROOMS- SECS. 303.2, 303.3, & 303.4 FBC
 P, AND SEC. 107.2.1 WPB. SPECS FOR THE FILL HOSE,
 CHEMICAL SINK, EMERGENCY SHOWER/EYEWASH STATION AND
 SUMP PUMPS NOT PROVIDED.
 D) FAILED. PLEASE NOTE THAT THE EYEWASH STATION SHALL
 CONFORM TO ISEA Z358.1, AND IF HOT AND COLD WATER ARE
 SUPPLIED TO THE STATION, THE TEMPERATURE OF THE WATER
 SUPPLY SHALL ONLY BE CONTROLLED BY A TEMPERATURE
 ACTUATED MIXING VALVE COMPLYING WITH ASSE 1071- SEE
 SECS. 411.1- 411.3 FBC P. THE ARCHITECT?S NARRATIVE
 STATES ONLY COLD WATER PROVIDED. PLEASE SUBMIT SPECS
 FOR THE FIXTURE TO VERIFY COMPLIANCE ACCORDING TO THE
 MANUFACTURER.
  
 11) P214) A-401 ROOF DRAINAGE:
 B) FAILED. PLEASE SEE TABLES 1106.3 & 1106.6 FBC P AND
 PROVIDE THE GPM CAPACITIES OF THE GUTTERS AND
 DOWNSPOUTS IN ORDER TO VERIFY SIZES ARE CODE COMPLIANT.
 NOT PROVIDED.
  
 12) FAILED- SECTION 309.2 FLOOD HAZARD. THE ARCHITECT?S
 RESPONSE TO THE COMMENT REFERENCES THE CIVIL PLANS.
 PLEASE PROVIDE MORE SPECIFIC INFORMATION REGARDING THE
 PLUMBING AND CHEMICAL CONTAINMENT AND PIPING SYSTEMS
 FOR BUILDING B. VERIFY THAT THE SYSTEMS ARE INSTALLED
 2FT. ABOVE THE BASE FLOOD ELEVATIONS HEIGHT OR HE
 SYSTEMS ARE DESIGNED AND INSTALLED TO PREVENT WATER
 FROM ENTERING OR ACCUMULATING WITHIN THEIR COMPONENTS
 AND THE SYSTEMS ARE CONSTRUCTED TO RESIST HYDROSTATIC
 AND HYDRODYNAMIC LOADS AND STRESSES, INCLUDING THE
 EFFECTS OF BUOYANCY, DURING THE OCCURRENCE OF FLOODING
 UP TO SUCH ELEVATION.
 FLOOD HAZARD: FOR STRUCTURES LOCATED IN FLOOD HAZARD
 AREAS, THE FOLLOWING SYSTEMS AND EQUIPMENT SHALL BE
 LOCATED AND INSTALLED AS REQUIRED BY SECTION 1612 OF
 THE FLORIDA BUILDING CODE, BUILDING, AND ASCE 24-14.
 1. WATER SERVICE PIPES.
 2. PUMP SEALS IN INDIVIDUAL WATER SUPPLY SYSTEMS WHERE
 THE PUMP IS LOCATED BELOW THE DESIGN FLOOD ELEVATION.
 3.COVERS ON POTABLE WATER WELLS SHALL BE SEALED, EXCEPT
 WHERE THE TOP OF THE CASING WELL OR PIPE SLEEVE IS
 ELEVATED TO NOT LESS THAN 1 FOOT (305 MM) ABOVE THE
 DESIGN FLOOD ELEVATION.
 4.SANITARY DRAINAGE PIPING.
 5.STORM DRAINAGE PIPING.
 6.MANHOLE COVERS SHALL BE SEALED, EXCEPT WHERE ELEVATED
 TO OR ABOVE THE DESIGN FLOOD ELEVATION.
 7.OTHER PLUMBING FIXTURES, FAUCETS, FIXTURE FITTINGS,
 PIPING SYSTEMS AND EQUIPMENT.
 8.WATER HEATERS.
 9.VENTS AND VENT SYSTEMS.
 EXCEPTION: THE SYSTEMS LISTED IN THIS SECTION ARE
 PERMITTED TO BE LOCATED BELOW THE ELEVATION REQUIRED BY
 SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING FOR
 UTILITIES AND ATTENDANT EQUIPMENT, PROVIDED THAT THE
 SYSTEMS ARE DESIGNED AND INSTALLED TO PREVENT WATER
 FROM ENTERING OR ACCUMULATING WITHIN THEIR COMPONENTS
 AND THE SYSTEMS ARE CONSTRUCTED TO RESIST HYDROSTATIC
 AND HYDRODYNAMIC LOADS AND STRESSES, INCLUDING THE
 EFFECTS OF BUOYANCY, DURING THE OCCURRENCE OF FLOODING
 UP TO SUCH ELEVATION.
 15A) PLEASE REVIEW ASCE 24-14 SEC. 7.3 PLUMBING SYSTEMS
 RELATING TO SYSTEMS IN FLOOD HAZARDS ZONES:
 SECTION 7.3.1: THE PLUMBING PIPES SHALL BE BURIED TO A
 DEPTH SUFFICIENT TO PREVENT MOVEMENT, SEPARATION, OR
 LOSS DUE TO FLOODING AND EROSION UNDER DESIGN FLOOD
 CONDITIONS.
 7.3.2: THE PLUMBING PIPING EMERGING FROM UNDERGROUND
 SHALL BE DESIGNED, CONSTRUCTED, ANCHORED, AND PROTECTED
 TO WITHSTAND FLOOD-RELATED LOADS, INCLUDING THE EFFECTS
 OF BUOYANCY, HYDRODYNAMIC FORCES, AND DEBRIS IMPACT.
 7.3.3: THE PLUMBING SYSTEM AND COMPONENTS SHALL BE
 ELEVATED AT A MINIMUM OF 2 FT. ABOVE THE BFE + 2 FT. OR
 THE DFE WHICHEVER IS HIGHER PER TABLE 7-1. OPENINGS
 BELOW THE REQUIRED ELEVATION SHALL BE PROTECTED WITH
 AUTOMATIC BACKWATER VALVES OR OTHER AUTOMATIC BACKFLOW
 DEVICES. DEVICES SHALL BE INSTALLED IN EACH LINE THAT
 EXTENDS BELOW THE DFE TO PREVENT RELEASE OF SEWAGE INTO
 FLOODWATERS AND TO PREVENT INFILTRATION BY FLOODWATERS
 INTO THE PLUMBING.
 7.3.4: SANITARY SYSTEM STORAGE TANKS SHALL BE DESIGNED,
 CONSTRUCTED, INSTALLED, AND ANCHORED TO RESIST AT LEAST
 1.5 TIMES THE POTENTIAL BUOYANT AND OTHER FLOOD FORCES
 ACTING ON AN EMPTY TANK DURING DESIGN FLOOD CONDITIONS.
 TANKS AND PIPING SHALL BE INSTALLED TO RESIST LOCAL
 SCOUR AND EROSION.
  
 16) FAILED. MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR ALL FIXTURES, APPLIANCES,
 EQUIPMENT, AND DEVICES SHALL BE REVIEWED AND APPROVED
 BY THE RESPONSIBLE DESIGN PROFESSIONAL IN CHARGE AND
 SUBMITTED FOR REVIEW. IF THE SUBMITTALS ARE TO BE
 DEFERRED, PLEASE PROVIDE A LIST ON THE PLANS- SEC.
 107.3.4.1 WPB. SPECS FOR THE FILL HOSE, CHEMICAL SINK,
 EMERGENCY SHOWER/EYEWASH STATION AND SUMP PUMPS NOT
 PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
  