Plan Review Notes
Plan Review Notes For Permit 21110362
Permit Number 21110362
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-21 09:33:321ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110362
 12/17/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2 NOTES 1 & 2: REFERENCE IS MADE TO SHEET P1.
 PLEASE SUBMIT THE SHEET- SEC. 107.2.1 WPB.
  
 2) P2 & P3: BASED ON THE DRAWING AN OIL/SAND SEPARATOR
 IS REQUIRED TO RECEIVE THE DRAINAGE FROM THE WASH PAD.
 REFER TO SECS. 1003.4- 1003.5 FBC P. PLEASE REVISE THE
 PLANS AND PROVIDE:
 A) SEPARATOR LOCATION.
 B) PLUMBING PIPING PLANS AND ISOMETRIC DRAWING.
 C) SEPARATOR EQUIPMENT SCHEDULE AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS APPROVED AND STAMPED BY
 THE ENGINEER OF RECORD.
 D) SEPARATOR SIZING CALCULATIONS.
  
 3) A1.01, P2 & P3: REFER TO SECS. 803.1 & 803.2 FBC P
 AND PROVIDE AN APPROVED CHEMICAL DILUTION OR
 NEUTRALIZING DEVICE AND SYSTEM FOR THE MIX/LOAD. REFER
 TO COMMENT #10 FOR FURTHER INFORMATION.
  
 4) P2 & P3: PLEASE SUBMIT CIVIL PLANS INCLUDING
 WATER/SEWER AND DRAINAGE PLANS. THE WATER/SEWER SHALL
 SHOW LOCATIONS OF WATER MAIN, POINT OF WATER SERVICE
 CONNECTION, METER AND BACKFLOW LOCATION, SEWER/BUILDING
 DRAIN POINT OF CONNECTION, AND LOCATION OF THE SEPTIC
 TANK. THE DRAINAGE PLANS SHALL SHOW STORM DRAIN LATERAL
 AND BUILDING STORM DRAIN POINTS OF CONNECTION, AND/OR
 LOCATIONS OF ROOF DRAINAGE AREAS, AND CATCH BASINS-
 SECS. 107.2.1, 110.9 WPB AND SEC. 1101.2 FBC PLEASE
 NOTE SEPARATE PERMITS ARE REQUIRED FOR:
 A) POTABLE WATER SERVICE BACKFLOW PREVENTER IRRIGATION,
 IRRIGATION SERVICE BACKFLOW PREVENTER.
 B) OIL INTERCEPTOR/SEPARATOR
 C) IRRIGATION
 D) IRRIGATION SERVICE BACKFLOW PREVENTER.
 E) FUEL TANKS
  
 6) BACKFLOW PREVENTION: IN ACCORDANCE WITH THE WEST
 PALM BEACH UTILITIES CROSS CONNECTION MANUAL AN RPZ
 BACKFLOW ASSEMBLY (REDUCED PRESSURE ZONE) SHALL BE
 INSTALLED ON THE POTABLE WATER SERVICE LINE. AS NOTED
 IN COMMENT #1 ABOVE, THE LOCATION OF THE RPZ SHALL BE
 SHOWN ON THE CIVIL PLANS AND MANUFACTURER'S
 SPECIFICATIONS SHALL BE SUBMITTED FOR REVIEW.
 PLEASE NOTE THAT FL. LICENSED PLUMBING CONTRACTORS
 SHALL OBTAIN SEPARATE PERMITS FOR INSTALLATION OF THE
 BACKFLOW PREVENTERS IN ACCORDANCE WITH SECTION 105.1
 WPB AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICES
 SHALL BE TESTED AND CERTIFIED BY THE WPB UTILITIES
 DEPARTMENT PRIOR TO FINAL INSPECTION BY THE BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT.AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 7) A1.01, P2, P3: PROVIDE THE USE AND OCCUPANCY
 CLASSIFICATION OF THE BUILDING, OCCUPANT LOAD, AND
 PLUMBING FIXTURE CALCULATIONS IN COMPLIANCE WITH TABLE
 403.1 FBC P.
  
 8) P2 & P3: SHOW THE LOCATIONS OF THE POTABLE WATER
 BACKFLOW PREVENTER AND OIL SEPARATOR ON THE PLANS- SEC.
 107.2.1 WPB.
  
 9) P2 & P3: PROVIDE A SANITARY DRAIN AND VENT LAYOUT
 PLAN AND ISOMETRIC DRAWING- SECS 107.2.1 & 107.3.5.1.3
 WPB.
  
 10) A1.01, P2 & P3: REFER TO SECS. 803.1 & 803.2 FBC P
 AND PROVIDE AN APPROVED CHEMICAL DILUTION OR
 NEUTRALIZING DEVICE FOR THE CHEMICAL WASTE IN THE
 MIX/LOAD ROOM. PLEASE EXPLAIN THE PROCESSES THAT WILL
 OCCUR IN THE ROOM AND PROVIDE AN ENLARGED CHEMICAL
 DRAIN AND VENT PIPING SCHEMATIC OR ISOMETRIC DRAWING
 THAT INCLUDES THE DRAINAGE CONNECTION FROM THE SYSTEM
 TO AN APPROVED PLACE OF DISPOSAL- SEC. 803.2 FBC P &
 SEC. 107.2.1 WPB.
 A) REVISE SHEETS P2 & P3 TO SHOW THE CHEMICAL SYSTEM
 DRAINAGE SYSTEM PIPING LAYOUT- 107.3.5.1.3 WPB.
 B) REVISE SHEETS P2 & P3 TO SHOW THE POTABLE WATER
 PIPING CONNECTIONS TO ALL FIXTURES IN THE MIX/LOAD ROOM
 INCLUDING THE EMERGENCY EYEWASH STATION, CHEMICAL SINK,
 AND CLOSED LOOP WASH SYSTEM. SHOW THE LOCATIONS OF
 REQUIRED WATER HAMMER ARRESTORS AND BACKFLOW PREVENTERS
 AND INCLUDE BACKFLOW SPECIFICATIONS AND LISTINGS- SECS.
 604.5, 608.3 & TABLE 608.3 FBC P.
 C) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL PIPING,
 FIXTURES AND EQUIPMENT IN THE MIX/LOAD AND FUELING
 STATION ROOMS- SECS. 303.2, 303.3, & 303.4 FBC P, AND
 SEC. 107.2.1 WPB.
 D) PLEASE NOTE THAT THE EYEWASH STATION SHALL CONFORM
 TO ISEA Z358.1, AND IF HOT AND COLD WATER ARE SUPPLIED
 TO THE STATION, THE TEMPERATURE OF THE WATER SUPPLY
 SHALL ONLY BE CONTROLLED BY A TEMPERATURE ACTUATED
 MIXING VALVE COMPLYING WITH ASSE 1071- SEE SECS. 411.1-
 411.3 FBC P.
  
 11) P214) A-401 ROOF DRAINAGE:
 A) INDICATE THE RAINFALL RATE USED AS THE BASIS OF THE
 CALCULATIONS- SEC. 1106.1 AND PROVIDE ROOF DRAINAGE
 CALCULATIONS BASED ON THE RATE- SECS. 1106.1- 1106.4
 FBC P.
 B) PLEASE SEE TABLES 1106.3 & 1106.6 FBC P AND PROVIDE
 THE GPM CAPACITIES OF THE GUTTERS AND DOWNSPOUTS IN
 ORDER TO VERIFY SIZES ARE CODE COMPLIANT.
 C) SHOW THE DOWNSPOUT DISCHARGE LOCATIONS. CLARIFY IF
 THE DOWNSPOUTS WILL CONNECT TO AN UNDERGROUND STORM
 DRAIN SYSTEM OR BE DISCHARGED TO GRADE. REFER TO
 COMMENT #3 AND PROVIDE CIVIL DRAWINGS SHOWING STORM
 DRAINAGE POINTS OF CONNECTIONS (IF APPLICABLE), OR
 REFER TO SEC. 1503.7 FBC B AND INDICATE THE DOWNSPOUTS
 WILL DISCHARGE AT LEAST 1 FOOT AWAY FROM THE BUILDING
 SIDE WALL TO APPROVED LOCATIONS OF DISPOSAL- SEC.
 1101.2 FBC P.
  
 12) FLOOD HAZARD: FOR STRUCTURES LOCATED IN FLOOD
 HAZARD AREAS, THE FOLLOWING SYSTEMS AND EQUIPMENT SHALL
 BE LOCATED AND INSTALLED AS REQUIRED BY SECTION 1612 OF
 THE FLORIDA BUILDING CODE, BUILDING, AND ASCE 24-14.
  
 1. WATER SERVICE PIPES.
 2. PUMP SEALS IN INDIVIDUAL WATER SUPPLY SYSTEMS WHERE
 THE PUMP IS LOCATED BELOW THE DESIGN FLOOD ELEVATION.
 3.COVERS ON POTABLE WATER WELLS SHALL BE SEALED, EXCEPT
 WHERE THE TOP OF THE CASING WELL OR PIPE SLEEVE IS
 ELEVATED TO NOT LESS THAN 1 FOOT (305 MM) ABOVE THE
 DESIGN FLOOD ELEVATION.
 4.SANITARY DRAINAGE PIPING.
 5.STORM DRAINAGE PIPING.
 6.MANHOLE COVERS SHALL BE SEALED, EXCEPT WHERE ELEVATED
 TO OR ABOVE THE DESIGN FLOOD ELEVATION.
 7.OTHER PLUMBING FIXTURES, FAUCETS, FIXTURE FITTINGS,
 PIPING SYSTEMS AND EQUIPMENT.
 8.WATER HEATERS.
 9.VENTS AND VENT SYSTEMS.
  
 EXCEPTION: THE SYSTEMS LISTED IN THIS SECTION ARE
 PERMITTED TO BE LOCATED BELOW THE ELEVATION REQUIRED BY
 SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING FOR
 UTILITIES AND ATTENDANT EQUIPMENT, PROVIDED THAT THE
 SYSTEMS ARE DESIGNED AND INSTALLED TO PREVENT WATER
 FROM ENTERING OR ACCUMULATING WITHIN THEIR COMPONENTS
 AND THE SYSTEMS ARE CONSTRUCTED TO RESIST HYDROSTATIC
 AND HYDRODYNAMIC LOADS AND STRESSES, INCLUDING THE
 EFFECTS OF BUOYANCY, DURING THE OCCURRENCE OF FLOODING
 UP TO SUCH ELEVATION.
  
 15A) PLEASE REVIEW ASCE 24-14 SEC. 7.3 PLUMBING SYSTEMS
 RELATING TO SYSTEMS IN FLOOD HAZARDS ZONES:
 SECTION 7.3.1: THE PLUMBING PIPES SHALL BE BURIED TO A
 DEPTH SUFFICIENT TO PREVENT MOVEMENT, SEPARATION, OR
 LOSS DUE TO FLOODING AND EROSION UNDER DESIGN FLOOD
 CONDITIONS.
 7.3.2: THE PLUMBING PIPING EMERGING FROM UNDERGROUND
 SHALL BE DESIGNED, CONSTRUCTED, ANCHORED, AND PROTECTED
 TO WITHSTAND FLOOD-RELATED LOADS, INCLUDING THE EFFECTS
 OF BUOYANCY, HYDRODYNAMIC FORCES, AND DEBRIS IMPACT.
 7.3.3: THE PLUMBING SYSTEM AND COMPONENTS SHALL BE
 ELEVATED AT A MINIMUM OF 2 FT. ABOVE THE BFE + 2 FT. OR
 THE DFE WHICHEVER IS HIGHER PER TABLE 7-1. OPENINGS
 BELOW THE REQUIRED ELEVATION SHALL BE PROTECTED WITH
 AUTOMATIC BACKWATER VALVES OR OTHER AUTOMATIC BACKFLOW
 DEVICES. DEVICES SHALL BE INSTALLED IN EACH LINE THAT
 EXTENDS BELOW THE DFE TO PREVENT RELEASE OF SEWAGE INTO
 FLOODWATERS AND TO PREVENT INFILTRATION BY FLOODWATERS
 INTO THE PLUMBING.
 7.3.4: SANITARY SYSTEM STORAGE TANKS SHALL BE DESIGNED,
 CONSTRUCTED, INSTALLED, AND ANCHORED TO RESIST AT LEAST
 1.5 TIMES THE POTENTIAL BUOYANT AND OTHER FLOOD FORCES
 ACTING ON AN EMPTY TANK DURING DESIGN FLOOD CONDITIONS.
 TANKS AND PIPING SHALL BE INSTALLED TO RESIST LOCAL
 SCOUR AND EROSION.
  
 16) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUALS FOR ALL FIXTURES, APPLIANCES, EQUIPMENT, AND
 DEVICES SHALL BE REVIEWED AND APPROVED BY THE
 RESPONSIBLE DESIGN PROFESSIONAL IN CHARGE AND SUBMITTED
 FOR REVIEW. IF THE SUBMITTALS ARE TO BE DEFERRED PLEASE
 PROVIDE A LIST ON THE PLANS- SEC. 107.3.4.1 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  