| 2022-03-14 13:39:14 | NEW BUILDING (B) |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | |
| | 1) ELEVATION CERTIFICATE - A2 - ADDRESS SHOULD BE THE |
| | SAME AS SHOWN BY THE ADDRESS REVIEW - 8101 GEORGIA AV |
| | |
| | 2) ELEVATION CERTIFICATE - C2(A) - ELEVATION SHOWN DOES |
| | NOT MATCH THE PROPOSED LOWEST FLOOR ELEVATION SHOWN ON |
| | THE DRAWINGS.(10.32 NAVD) |
| | |
| | 3) PLEASE PROVIDE THE REQUIRED DOCUMENTATION PER FBC |
| | 1612.5 FLOOD HAZARD DOCUMENTATION. |
| | |
| | THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND |
| | SEALED BY A REGISTERED DESIGN PROFESSIONAL AND |
| | SUBMITTED TO THE BUILDING OFFICIAL: |
| | |
| | 1.FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN |
| | COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES: |
| | |
| | 1.2.FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD |
| | ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC |
| | ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM |
| | REQUIREMENTS IN SECTION 2.7.2.1 OF ASCE 24, |
| | CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT |
| | THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC |
| | FLOOD FORCES IN ACCORDANCE WITH SECTION 2.7.2.2 OF ASCE |
| | 24. |
| | |
| | 1.3.FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS, |
| | CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT |
| | THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH |
| | ASCE 24. |
| | |
| | |