| 2021-12-17 16:26:56 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110361 |
| | 12/17/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A-401 ROOF DRAINAGE: |
| | A) INDICATE THE RAINFALL RATE USED AS THE BASIS OF THE |
| | CALCULATIONS- SEC. 1106.1 AND PROVIDE ROOF DRAINAGE |
| | CALCULATIONS BASED ON THE RATE- SECS. 1106.1- 1106.4 |
| | FBC P. |
| | B) PLEASE SEE TABLES 1106.3 & 1106.6 FBC P AND PROVIDE |
| | THE GPM CAPACITIES OF THE GUTTERS AND DOWNSPOUTS IN |
| | ORDER TO VERIFY SIZES ARE CODE COMPLIANT. |
| | C) SHOW THE DOWNSPOUT DISCHARGE LOCATIONS. CLARIFY IF |
| | THE DOWNSPOUTS WILL CONNECT TO AN UNDERGROUND STORM |
| | DRAIN SYSTEM OR BE DISCHARGED TO GRADE. REFER TO |
| | COMMENT #1 UNDER PERMIT 21110360 FOR THE MAINTENANCE |
| | BUILDING AND PROVIDE CIVIL DRAWINGS SHOWING STORM |
| | DRAINAGE POINTS OF CONNECTIONS (IF APPLICABLE), OR |
| | REFER TO SEC. 1503.7 FBC B AND INDICATE THE DOWNSPOUTS |
| | WILL DISCHARGE AT LEAST 1 FOOT AWAY FROM THE BUILDING |
| | SIDE WALL TO APPROVED LOCATIONS OF DISPOSAL- SEC. |
| | 1101.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |