Plan Review Notes
Plan Review Notes For Permit 21110360
Permit Number 21110360
Review Stop P
Sequence Number 2
Notes
Date Text
2022-02-11 12:50:202ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110360
 2/11/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P4: THE REQUIRED EXPANSION TANK SHOWN ON THE
 PREVIOUS PLAN SUBMITTAL OR THE WATER HEATER WAS REMOVED
 FROM THE RESUBMITTED PLAN. PLEASE RESUBMIT THE
 CORRECTED DETAIL WITH THE EXPANSION TANK IN PLACE- SEC.
 607.3 FBC P.
  
 2) A-103: THE MEASUREMENTS FOR THE GRAB BARS AT THE
 WATER CLOSETS AND SHOWERS SHALL BE SHOWN TO THE TOPS OF
 THE GRIPPING SURFACES- SEC. 609.4 FBC ACC. (COMMENT #10
 F FROM THE 1ST REVIEW).
  
 3) A-103: PLEASE SHOW THE GRAB BAR ON THE SHOWER BACK
 WALL WILL EXTEND 18-INCHES FROM THE CONTROL WALL- SEC.
 608.3.1 FBC ACC.(COMMENT #10 J FROM THE 1ST REVIEW).
  
 4 A-103: PLEASE PROVIDE A SHOWER SEAT DETAIL SHOWING
 THE REQUIRED EDGE CLEARANCES AS SHOWN IN FIGURE 610.3.2
 FBC ACC. (COMMENT #10 M FROM THE 1ST REVIEW).
  
 5) A-401: PLEASE PROVIDE THE GPM CAPACITIES OF THE
 GUTTERS AND DOWNSPOUTS IN ORDER TO VERIFY SIZES ARE
 CODE COMPLIANT- SEE TABLE 1106.3 & 1106.6 FBC B.
 (COMMENT #14 B FROM THE 1ST REVIEW).
  
 6) LS1.01: PLEASE REVISE THE CALCULATIONS TO INCLUDE
 ALL EMPLOYEES ASSOCISATED WITH BUILDINGS B & C- SEC.
 403.3 FBC P.
  
 7) SHEET P1- COMMENT #15 FROM THE 1ST REVIEW- FLOOD
 HAZARD. THE NEW SURVEY SHOWS THE BUILDING IS LOCATED IN
 AN AE FLOOD HAZARD ZONE. PLEASE CLARIFY IF ANY OF THE
 BUILDING PLUMBING COMPONENTS- SANITARY LINE, SEPTIC
 TANK, POTABLE WATER LINE AND BACKFLOW PREVENTER ARE
 LOCATED LESS THAN 2 FT. BELOW THE FLOOD ELEVATION
 HEIGHT. PLEASE REVIEW THE FOLLOWING REQUIREMENTS AND
 PROVIDE COMPLIANCE DETAILS AND DRAWINGS WHERE
 APPLICABLE.
 FLOOD HAZARD: FOR STRUCTURES LOCATED IN FLOOD HAZARD
 AREAS, THE FOLLOWING SYSTEMS AND EQUIPMENT SHALL BE
 LOCATED AND INSTALLED AS REQUIRED BY SECTION 1612 OF
 THE FLORIDA BUILDING CODE, BUILDING, AND ASCE 24-14.
 1. WATER SERVICE PIPES.
 2. PUMP SEALS IN INDIVIDUAL WATER SUPPLY SYSTEMS WHERE
 THE PUMP IS LOCATED BELOW THE DESIGN FLOOD ELEVATION.
 3.COVERS ON POTABLE WATER WELLS SHALL BE SEALED, EXCEPT
 WHERE THE TOP OF THE CASING WELL OR PIPE SLEEVE IS
 ELEVATED TO NOT LESS THAN 1 FOOT (305 MM) ABOVE THE
 DESIGN FLOOD ELEVATION.
 4.SANITARY DRAINAGE PIPING.
 5.STORM DRAINAGE PIPING.
 6.MANHOLE COVERS SHALL BE SEALED, EXCEPT WHERE ELEVATED
 TO OR ABOVE THE DESIGN FLOOD ELEVATION.
 7.OTHER PLUMBING FIXTURES, FAUCETS, FIXTURE FITTINGS,
 PIPING SYSTEMS AND EQUIPMENT.
 8.WATER HEATERS.
 9.VENTS AND VENT SYSTEMS.
 EXCEPTION: THE SYSTEMS LISTED IN THIS SECTION ARE
 PERMITTED TO BE LOCATED BELOW THE ELEVATION REQUIRED BY
 SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING FOR
 UTILITIES AND ATTENDANT EQUIPMENT, PROVIDED THAT THE
 SYSTEMS ARE DESIGNED AND INSTALLED TO PREVENT WATER
 FROM ENTERING OR ACCUMULATING WITHIN THEIR COMPONENTS
 AND THE SYSTEMS ARE CONSTRUCTED TO RESIST HYDROSTATIC
 AND HYDRODYNAMIC LOADS AND STRESSES, INCLUDING THE
 EFFECTS OF BUOYANCY, DURING THE OCCURRENCE OF FLOODING
 UP TO SUCH ELEVATION.
  
 PLEASE REVIEW ASCE 24-14 SEC. 7.3 PLUMBING SYSTEMS
 RELATING TO SYSTEMS IN FLOOD HAZARDS ZONES:
 SECTION 7.3.1: THE PLUMBING PIPES SHALL BE BURIED TO A
 DEPTH SUFFICIENT TO PREVENT MOVEMENT, SEPARATION, OR
 LOSS DUE TO FLOODING AND EROSION UNDER DESIGN FLOOD
 CONDITIONS.
 7.3.2: THE PLUMBING PIPING EMERGING FROM UNDERGROUND
 SHALL BE DESIGNED, CONSTRUCTED, ANCHORED, AND PROTECTED
 TO WITHSTAND FLOOD-RELATED LOADS, INCLUDING THE EFFECTS
 OF BUOYANCY, HYDRODYNAMIC FORCES, AND DEBRIS IMPACT.
 7.3.3: THE PLUMBING SYSTEM AND COMPONENTS SHALL BE
 ELEVATED AT A MINIMUM OF 2 FT. ABOVE THE BFE + 2 FT. OR
 THE DFE WHICHEVER IS HIGHER PER TABLE 7-1. OPENINGS
 BELOW THE REQUIRED ELEVATION SHALL BE PROTECTED WITH
 AUTOMATIC BACKWATER VALVES OR OTHER AUTOMATIC BACKFLOW
 DEVICES. DEVICES SHALL BE INSTALLED IN EACH LINE THAT
 EXTENDS BELOW THE DFE TO PREVENT RELEASE OF SEWAGE INTO
 FLOODWATERS AND TO PREVENT INFILTRATION BY FLOODWATERS
 INTO THE PLUMBING.
 7.3.4: SANITARY SYSTEM STORAGE TANKS SHALL BE DESIGNED,
 CONSTRUCTED, INSTALLED, AND ANCHORED TO RESIST AT LEAST
 1.5 TIMES THE POTENTIAL BUOYANT AND OTHER FLOOD FORCES
 ACTING ON AN EMPTY TANK DURING DESIGN FLOOD CONDITIONS.
 TANKS AND PIPING SHALL BE INSTALLED TO RESIST LOCAL
 SCOUR AND EROSION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719