| Date |
Text |
| 2021-12-10 07:09:35 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21110360 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SHOW THE OUTDOOR AIR INTAKE FOR AHU-1 IS 10 |
| | FEET AWAY FROM THE JANITOR AND LOCKER ROOM EXHAUST. FBC |
| | M 501.3.1-3 |
| | |
| | 2) PLEASE SHOW THAT THE EXHAUST FANS FOR THE GARAGE |
| | AREA WILL MEET THE TERMINATION LOCATION 10 FEET FROM |
| | FBC M 501.3.1-2 |
| | |
| | 3) PLEASE SHOW THE LOCKER ROOMS SQ FT CALCULATIONS FOR |
| | THE REQUIRED EXHAUST AIR. FBC M TABLE 403.3.1.1 |
| | |
| | 4) PLEASE CLASSIFY THE EQUIPMENT STORAGE AREA BY |
| | OCCUPANCY CLASSIFICATION FROM FBC M TABLE 403.3.1.1. IS |
| | THE USE OF SPACE COMPARED TO A PARKING GARAGE? HOW IS |
| | THIS SPACE GOING TO BE USED? THERE IS A MECHANICS WORK |
| | AREA, PLEASE SHOW THIS AREA MEETS THE EXHAUST |
| | REQUIREMENTS OF FBC M TABLE 403.3.1.1 |
| | |
| | 5) PLEASE SHOW THE BREAKROOM IN THE OUTDOOR AIR |
| | CALCULATIONS. IS THIS AREA TO BE USED MORE FOR A DINING |
| | ROOM? FBC M TABLE 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |