| Plan Review Notes For Permit 21110360 |
| Permit Number |
21110360 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-10 16:08:06 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) | | | OR | | | BRANCH CIRCUIT(S). | | | (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S) | | | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A | | | GROUNDING | | | ELECTRODE OR GROUNDING ELECTRODE SYSTEM INSTALLED IN | | | ACCORDANCE WITH PART III OF ARTICLE 250. THE GROUNDING | | | ELECTRODE | | | CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH | | | 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING | | | ELECTRODE, | | | THE GROUNDING ELECTRODE(S) REQUIRED IN 250.50 SHALL BE | | | INSTALLED. |
|