| Plan Review Notes For Permit 21110352 |
| Permit Number |
21110352 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-28 11:31:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED PLANS ARE BLURRY AND UNREADABLE AND | | | COULD NOT BE REVIEWED. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE CLEAR AND | | | READABLE PLAN SHEETS. | | | | | | | | | 2) THERE IS NO DOOR SCHEDULE ON THE SUBMITTED PLANS | | | THAT CAN CLEARLY INDICATE SIZE, LOCATION, FIRE RATING | | | AND DOOR HARDWARE. | | | | | | PLEASE PROVIDE A DOOR SCHEDULE INCLUDING THE SPEEFICS | | | OF EACH DOOR. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|