Plan Review Notes
Plan Review Notes For Permit 21110342
Permit Number 21110342
Review Stop M
Sequence Number 2
Notes
Date Text
2022-01-05 07:16:58PLEASE ADDRESS COMMENT BELOW FROM THE 1ST REVIEW CYCLE.
  
 PLEASE PROVIDE INFORMATION ON THE KITCHEN HOOD, SIZE OF
 DUCT, CFM'S OF EXHAUST, TERMINATION LOCATION, IS MAKE
 UP AIR REQUIRED? FBC 107.2.1
  
 THE REVISED DRAWING INDICATES A 24 X 24 INCH RETURN AIR
 GRILL @ 12 INCHES A.F.F.; PLEASE SHOW THIS MORE CLEAR
 AS IT APPEARS THAT IT WILL BE IN THE DOOR SEPARATING
 THE GARAGE FROM THE HOUSE, THIS CANNOT BE AS THE RETURN
 AIR CANNOT BE FROM THE GARAGE. FBC RES M1602.2-4
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  