| Plan Review Notes For Permit 21110342 |
| Permit Number |
21110342 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-01-05 07:16:58 | PLEASE ADDRESS COMMENT BELOW FROM THE 1ST REVIEW CYCLE. | | | | | | PLEASE PROVIDE INFORMATION ON THE KITCHEN HOOD, SIZE OF | | | DUCT, CFM'S OF EXHAUST, TERMINATION LOCATION, IS MAKE | | | UP AIR REQUIRED? FBC 107.2.1 | | | | | | THE REVISED DRAWING INDICATES A 24 X 24 INCH RETURN AIR | | | GRILL @ 12 INCHES A.F.F.; PLEASE SHOW THIS MORE CLEAR | | | AS IT APPEARS THAT IT WILL BE IN THE DOOR SEPARATING | | | THE GARAGE FROM THE HOUSE, THIS CANNOT BE AS THE RETURN | | | AIR CANNOT BE FROM THE GARAGE. FBC RES M1602.2-4 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|