Plan Review Notes
Plan Review Notes For Permit 21110342
Permit Number 21110342
Review Stop E
Sequence Number 2
Notes
Date Text
2022-01-05 14:07:20ELECTRIC PLAN REVIEW FAILED
  
 1) TANKLESS WATER HEATER LOADS AND OVERCURRENT
 PROTECTION APPEAR TO BE INCORRECTLY STATED. (1) 40-AMP
 2 POLE BREAKER SERVING A 18KW LOAD AND (1) SINGLE POLE
 40-AMP BREAKER SERVING A 7.3KW LOAD NEC 422.11 (E)
 2) STATED LOAD FOR AIR HANDLER HEAT STRIPS APPEAR TO BE
 INCORRECT.PANEL SCHEDULE STATES A 7.5KW HEAT STRIP,
 LOAD IS STATED AT 4.6KW. F.B.C.107.2
 3) PLAN DOES NOT APPEAR TO DETAIL CORRECTLY CARBON
 MONOXIDE DETECTORS WITHIN 10' OF BEDROOMS. FBC R315
 4)IT APPEARS THE PLANS AND ELECTRIC RISER DIAGRAM ARE
 CONFLICTING. NO MAIN DISCONNECT IS SHOWN ON RISER AND
 ONE IS SHOWN ON 1ST FLOOR ELECTRIC PLAN. PLEASE CORRECT
 THE CONFLICT. BE SURE TO DETAIL PROPER SYSTEM BONDING
 AS PER NEC.250.30(A)(1) FBC107.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  