Plan Review Notes
Plan Review Notes For Permit 21110342
Permit Number 21110342
Review Stop P
Sequence Number 1
Notes
Date Text
2021-11-23 13:35:011ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 21110342
 11/23/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A101: THE NOTES ON THE PLAN INDICATE THE
 GARAGE IS IN A FLOOD ZONE. REFER TO SECTION R322.1.6
 FBC RES AND PROVIDE NOTES ON THE PLAN TO INDICATE THE
 PLUMBING FIXTURES AND APPLIANCES ARE LOCATED AT OR
 ABOVE THE FLOOD ELEVATION HEIGHT. PLEASE REVIEW THE
 FOLLOWING CODE SECTIONS FROM THE ASCE- 2014 AND PROVIDE
 NOTES ON THE PLAN APPLICABLE TO THE PLUMBING
 INSTALLATIONS.
 SECTION 7.3.1: THE PLUMBING PIPES SHALL BE BURIED TO A
 DEPTH SUFFICIENT TO PREVENT MOVEMENT, SEPARATION, OR
 LOSS DUE TO FLOODING AND EROSION UNDER DESIGN FLOOD
 CONDITIONS.
 SECTION 7.3.2: THE PLUMBING PIPING EMERGING FROM
 UNDERGROUND SHALL BE DESIGNED, CONSTRUCTED, ANCHORED,
 AND PROTECTED TO WITHSTAND FLOOD-RELATED LOADS,
 INCLUDING THE EFFECTS OF BUOYANCY, HYDRODYNAMIC FORCES,
 AND DEBRIS IMPACT.
 SECTION 7.3.3: THE PLUMBING SYSTEM AND COMPONENTS (POOL
 EQUIPMENT) SHALL BE ELEVATED AT A MINIMUM OF 1 FT.
 ABOVE THE BFE + 1 FT. OR THE DFE WHICHEVER IS HIGHER
 PER TABLE 7-1. OPENINGS BELOW THE REQUIRED ELEVATION
 SHALL BE PROTECTED WITH AUTOMATIC BACKWATER VALVES OR
 OTHER AUTOMATIC BACKFLOW DEVICES.
  
 2) P102: THE ASSE 1070 APPLIES TO THE BATHTUB FAUCET
 TEMPERATURE LIMITING DEVICE BUT NOT THE SHOWER VALVE
 WHICH SHALL BE A PRESSURE-BALANCE, THERMOSTATIC-MIXING
 OR COMBINATION PRESSURE-BALANCE/THERMOSTATIC-MIXING
 VALVE TYPES WITH A HIGH LIMIT STOP IN ACCORDANCE WITH
 ASSE 1016/ASME A112.1016/CSA B125.16- SECTION P2708.4
 FBC RES.
  
 3) P103: PROVIDE THE EFFICIENCY RATINGS FOR THE WATER
 HEATERS AND SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALL MANUALS- TABLE C404.2 FBC EC.
  
 4) SEPARATE PERMITS ARE REQUIRED FOR THE POTABLE WATER
 SERVICE BACKFLOW PREVENTER, AND THE IRRIGATION SYSTEM.
 PLEASE PLACE NOTES ON THE PLAN FOR CLARIFICATION-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  