| 2021-11-18 10:28:17 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21110323 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE EXPLAIN WHAT IS BEING PRODUCED IN THIS LAB. | | | | | | 2) PLEASE PROVIDE THE SPECIFICATIONS FOR THE EXHAUST | | | AND RETICULATING HOOD: AXIOM 304610100. FBC 107.2.1 | | | | | | 3) PLEASE SHOW THE REQUIRED EXHAUST FOR LABS 2 AND 4. | | | FBC M TABLE 403.3.1.1 | | | | | | 4) PLEASE EXPLAIN WHY THE EXHAUST HOODS ARE REQUIRED. | | | FBC M 510 | | | | | | 5) PLEASE PROVIDE THE HEALTH HAZARDS PER NFPA 704-2017. | | | FBC M 510.1 | | | | | | 6) PLEASE EXPLAIN THE FLOW OF AIR THROUGH RC, IS THIS A | | | FILTER SYSTEM? | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|