| 2021-12-01 14:44:16 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | COMMENT #3 FROM 1ST REVIEW HAS NOT BEEN ADDRESSED. | | | | | | 3. **ADDITIONAL REQUIREMENTS FOR 20X50 FT. TENT*** | | | FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN | | | OF 40 FEET OR GREATER IN ANY DIRECTION: | | | | | | A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE | | | BASEPLATE/TIEDOWN DETAILS. | | | B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. | | | | | | THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY | | | A DESIGN PROFESSIONAL. | | | | | | NO EXCEPTIONS BY ORDER OF THE BUILDING OFFICIAL | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|