| Plan Review Notes For Permit 21110245 |
| Permit Number |
21110245 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-12-13 16:33:22 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, ITEM # 2 OF THE LAST REVIEW STILL LEAVES | | | SOME UNANSWERED QUESTIONS AS PER COMMENTS BELOW: | | | | | | A.) SLIDING GLASS DOOR AT OPENING #3 APPEARS TO BE IN A | | | ZONE 5 AREA AS IT IS CLEARLY CLOSE TO THE EDGE OF THE | | | WALL. | | | B.) PLEASE CONFIRM THAT THE CURVATURE OF THE BUILDING | | | HAS BEEN TAKEN INTO CONSIDERATION IN CALCULATING THE | | | DESIGN WIND PRESSURES AND THAT ALL WINDOW/DOOR | | | LOCATIONS ARE NOT IN ZONE 5. | | | | | | |
|