| 2021-12-21 13:49:16 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21110234 |
| | 12/21/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR BEARING THE REVIEW AND APPROVAL STAMP OF THE |
| | DESIGN PROFESSIONAL OF RECORD- SECS. 107.2.1 & 107.3.4 |
| | WPB. THE SPECS SHALL INDICATE THE GENERATOR IS UL 2200 |
| | APPROVED- SEC. 616.1 FBC FG. |
| | |
| | 2) GAS PIPING: |
| | A) PROVIDE A GAS PIPING CONNECTION DETAIL OR ISOMETRIC |
| | DRAWING SHOWING THE TYPE AND SIZE OF EXISTING GAS |
| | PIPING, LOCATION OF NEW OR EXISTING REGULATOR, SHUTOFF |
| | VALVE, PIPE UNIONS, AND NEW FLEX CONNECTOR TO THE |
| | GENERATOR-107.3.5.1.3 WPB. SUBMIT SPECS FOR THE FLEX |
| | CONNECTOR REVIEWED AND APPROVED BY THE DESIGN |
| | PROFESSIONAL OF RECORD- SECS. 411.1.3, 411.1.5, & 616.2 |
| | FBC FG. |
| | |
| | B) PROVIDE THE SYSTEM AND INLET PRESSURE AT THE |
| | REGULATOR, AND OUTPUT PRESSURE AT THE GENERATOR. SUBMIT |
| | SPECS FOR THE REGULATOR REVIEWED AND APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD- SEC. 410.2 FBC FG. |
| | |
| | C) VERIFY THE EXISTING GAS PIPING SERVING THE GENERATOR |
| | IS CONNECTED ON THE SUPPLY SIDE (UPSTREAM) OF THE MAIN |
| | GAS SHUTOFF VALVE AND MARKED AS SUPPLYING AN EMERGENCY |
| | GENERATOR- SEC. 7.9.7 NFPA 110. |
| | |
| | D) VERIFY THE BUILDING'S MAIN GAS SHUTOFF VALVE IS |
| | MARKED OR TAGGED TO INDICATE THE EXISTENCE OF THE |
| | SEPARATE EPS (GENERATOR) SHUTOFF VALVE- SEC. 7.9.8 NFPA |
| | 110. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |