| 2022-01-05 11:31:27 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110233 |
| | 1/5/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A123 DETAIL 2: THE TOILET PAPER DISPENSERS |
| | SHALL BE LOCATED 7 INCHES MINIMUM AND 9 INCHES MAXIMUM |
| | IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| | CENTERLINES OF THE DISPENSERS- SEC. AND FIGURE 604.7 |
| | FBC P. |
| | |
| | 2) P110: PLEASE RELOCATE THE FIXTURE DRAIN LINE FOR THE |
| | FLOOR DRAIN IN THE KITCHEN AREA TO THE GREASE WASTE |
| | LINE- SEC. 1003.3.1 FBC P. |
| | |
| | 3) P120: THE CONDENSATE DRAINAGE FROM THE RTU?S SHALL |
| | BE PIPED TO AN APPROVED PLACE OF DISPOSAL, AND SHALL |
| | NOT FLOW OUT ONTO THE ROOF SURFACE- SEC. 314.2.1 FBC P. |
| | |
| | 4) P001 & P120: SHOW THE LOCATIONS OF THE ICE MAKER |
| | BFP, AND THE RPZ. PLEASE NOTE THAT A SEPARATE PERMIT IS |
| | REQUIRED FOR NEW OR REPLACEMENT POTABLE WATER SERVICE |
| | BACKFLOW PREVENTERS- SECTION 105.1 & 107.1 WPB. |
| | |
| | 5) P 120 & P430 DETAIL 8: PROVIDE A BACKFLOW PREVENTER |
| | FOR THE FEED WATER SUPPLY LINE UPSTREAM OF THE FILTERS- |
| | SEC. 608.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |