Plan Review Notes
Plan Review Notes For Permit 21110233
Permit Number 21110233
Review Stop P
Sequence Number 2
Notes
Date Text
2022-01-05 11:31:272ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110233
 1/5/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A123 DETAIL 2: THE TOILET PAPER DISPENSERS
 SHALL BE LOCATED 7 INCHES MINIMUM AND 9 INCHES MAXIMUM
 IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINES OF THE DISPENSERS- SEC. AND FIGURE 604.7
 FBC P.
  
 2) P110: PLEASE RELOCATE THE FIXTURE DRAIN LINE FOR THE
 FLOOR DRAIN IN THE KITCHEN AREA TO THE GREASE WASTE
 LINE- SEC. 1003.3.1 FBC P.
  
 3) P120: THE CONDENSATE DRAINAGE FROM THE RTU?S SHALL
 BE PIPED TO AN APPROVED PLACE OF DISPOSAL, AND SHALL
 NOT FLOW OUT ONTO THE ROOF SURFACE- SEC. 314.2.1 FBC P.
  
 4) P001 & P120: SHOW THE LOCATIONS OF THE ICE MAKER
 BFP, AND THE RPZ. PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR NEW OR REPLACEMENT POTABLE WATER SERVICE
 BACKFLOW PREVENTERS- SECTION 105.1 & 107.1 WPB.
  
 5) P 120 & P430 DETAIL 8: PROVIDE A BACKFLOW PREVENTER
 FOR THE FEED WATER SUPPLY LINE UPSTREAM OF THE FILTERS-
 SEC. 608.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  