Plan Review Notes
Plan Review Notes For Permit 21110233
Permit Number 21110233
Review Stop M
Sequence Number 2
Notes
Date Text
2022-01-03 16:11:28THE PERMIT RESPONSE LETTER STATES THAT THE DESIGNER HAS
 ADDED CONDENSATE DRAINAGE NOTE TO SHEET M150 IN
 REFERENCE TO COMMENT 6 OF THE 1ST REVIEW CYCLE LISTED
 BELOW. THIS REVIEWER DOES NOT SEE A NOTE ON M150 THAT
 MENTIONS THE CONDENSATE DRAINAGE. PLEASE CORRECT THIS.
  
 6) PLEASE SHOW THE CONDENSATE DRAIN SIZE, MATERIAL AND
 TERMINATION LOCATION FOR ALL CONDENSATION. FBC M 307
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER