Plan Review Notes
Plan Review Notes For Permit 21110233
Permit Number 21110233
Review Stop P
Sequence Number 1
Notes
Date Text
2021-11-29 14:51:051ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110233
 11/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A123- FBC ACC COMPLIANCES REQUIRED:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) THE SIDE WALL GRAB BARS SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL-
 SECTION AND FIGURE 604.5.1
 E) THE REAR WALL GRAB BARS SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE- SECTION AND FIGURE 604.5.2.
 F) REMOVE THE VERTICAL GRAB BARS. THEY ARE NOT REQUIRED
 AND IN CONFLICT WITH SECTION 609.4 WHICH REQUIRES GRAB
 BARS TO BE INSTALLED IN HORIZONTAL POSITIONS.
 G) SHOW THE 3'-4" MEASUREMENT TO THE REFLECTIVE
 SURFACES OF THE MIRRORS- 603.3.
  
 2) P110: THE MOP SINK SHALL DRAIN INTO THE GREASE WASTE
 INTERCEPTOR LINE- SECTION 1003.3.1 FBC P.
  
 3) P110: PROVIDE A VENT FOR THE FLOOR DRAIN SHOWN BY
 THE FOOD PREP AREA- SECTION AND TABLE 909.1 FBC P.
  
 4) P110: THE CLEAR WATER DRAINAGE FROM THE ICE BIN (P4)
 SHALL NOT DISCHARGE INTO THE GREASE WASTE INTERCEPTOR-
 SECTION 1003.3.1 FBC P.
  
 5) P120: PROVIDE WATER HAMMER ARRESTOR SYMBOLS ON THE
 WATER ISOMETRIC DRAWING- SECTION 604.9 FBC P.
  
 6) P120: PROVIDE ENLARGED WATER FILTER PIPING DRAWINGS
 INDICATING COMPLIANCE WITH SECTIONS 608.3 & 608.4 FBC
 P.
  
 7) P001 & P120: SHOW THE LOCATIONS OF THE ICE MAKER
 BFP, AND THE RPZ. PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR NEW OR REPLACEMENT POTABLE WATER SERVICE
 BACKFLOW PREVENTERS- SECTION 105.1 & 107.1 WPB.
  
 8) P120: THE PLAN SHOWS NON-COMPLIANCE WITH SECTION &
 TABLE C404.5.1 FBC EC. A 1/2 INCH HW PIPE HAS A MAXIMUM
 ALLOWABLE LENGTH OF 2FT. FROM THE NEAREST HOT WATER
 SOURCE TO THE FIXTURE SUPPLY PIPE AT THE LAVATORIES.
 PLEASE PROVIDE EITHER POINT OF USE WATER HEATERS AT THE
 LAVATORIES OR A HOT WATER RECIRCULATION PUMP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  