Plan Review Notes
Plan Review Notes For Permit 21110233
Permit Number 21110233
Review Stop M
Sequence Number 1
Notes
Date Text
2021-11-17 08:33:511ST REVIEW FBC-2020 MECHANICAL
 PERMIT- 21110233
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE
 REFRIGERATION EQUIPMENT MUST HAVE A SEPARATE PERMIT
 APPLICATION, SEPARATE PLAN REVIEW AND DOCUMENTATION FOR
 THE REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS
 PERMIT.
  
 2) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE
 KITCHEN HOOD EQUIPMENT MUST HAVE A SEPARATE PERMIT
 APPLICATION, SEPARATE PLAN REVIEW AND DOCUMENTATION FOR
 THE REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS
 PERMIT.
  
 3) PLEASE PROVIDE DOCUMENTATION FOR THE APPLIANCE THAT
 WOULD REQUIRE THE TYPE I HOOD OR PROVIDE THE
 DOCUMENTATION TO MEET THE EXCEPTION OF FBC M 507.2
  
 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 5) PLEASE EXPLAIN THE LOCATION OF EF-4 AND THE USE OF
 THIS EXHAUST FAN. FBC 107.2.1
  
 6) PLEASE SHOW THE CONDENSATE DRAIN SIZE, MATERIAL AND
 TERMINATION LOCATION FOR ALL CONDENSATION. FBC M 307
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  