| 2021-11-17 08:33:51 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT- 21110233 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE |
| | REFRIGERATION EQUIPMENT MUST HAVE A SEPARATE PERMIT |
| | APPLICATION, SEPARATE PLAN REVIEW AND DOCUMENTATION FOR |
| | THE REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS |
| | PERMIT. |
| | |
| | 2) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE |
| | KITCHEN HOOD EQUIPMENT MUST HAVE A SEPARATE PERMIT |
| | APPLICATION, SEPARATE PLAN REVIEW AND DOCUMENTATION FOR |
| | THE REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS |
| | PERMIT. |
| | |
| | 3) PLEASE PROVIDE DOCUMENTATION FOR THE APPLIANCE THAT |
| | WOULD REQUIRE THE TYPE I HOOD OR PROVIDE THE |
| | DOCUMENTATION TO MEET THE EXCEPTION OF FBC M 507.2 |
| | |
| | 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC EC C403.2.1 |
| | |
| | 5) PLEASE EXPLAIN THE LOCATION OF EF-4 AND THE USE OF |
| | THIS EXHAUST FAN. FBC 107.2.1 |
| | |
| | 6) PLEASE SHOW THE CONDENSATE DRAIN SIZE, MATERIAL AND |
| | TERMINATION LOCATION FOR ALL CONDENSATION. FBC M 307 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |