Plan Review Notes
Plan Review Notes For Permit 21110233
Permit Number 21110233
Review Stop G
Sequence Number 1
Notes
Date Text
2021-11-29 15:29:001ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21110233
 11/29/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P120: PROVIDE A COMPLETE GAS RISER DRAWING
 THAT INCLUDES ALL NEW AND EXISTING GAS PIPING SERVING
 APPLIANCES AND EQUIPMENT- SECTIONS 401.3 & 401.4 FBC
 FG. REFER TO FBC CHAPTER 4 FUEL FBC- THE RISER SHALL
 INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) P120: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR
 THE WATER HEATER INDICATING THE MAKE AND MODEL, BTU
 CAPACITY, INPUT PRESSURE, AND EFFICIENCY RATING-
 SECTION 624.1 FBC FG, AND TABLE C404.1 FBC EC.
  
 3) P120: SHOW THE WATER HEATER DIRECT VENT COMBUSTION
 AIR INTAKE DUCT AND VENT RUNS AND TERMINATION
 LOCATIONS- SECTIONS 503.2.3, 503.6.5 & 624.1 FBC FG.
  
 4) P120: PROVIDE A ULL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAIL FOR SEALING THE ANNUAL SPACE AROUND THE
 GAS PIPE WALL AND ROOF PENETRATIONS- SECTION 714.4.1.2
 FBC B.
  
 5) P120: PROVIDE A PIPE SUPPORT DETAIL FOR THE GAS
 PIPING ON THE ROOF- SECTION 404.9 FBC FG.
  
 6) P120: PLEASE REMOVE THE IFGC 2012 REFERENCE FROM THE
 PLAN NOTE. THE PROPOSED GAS INSTALLATIONS SHALL BE IN
 COMPLIANCE WITH THE FLORIDA FUEL GAS CODE 7TH EDITION
 2020.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  