| 2022-02-23 14:49:24 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21110232 |
| | 2/9/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENT # 1 FROM |
| | THE 1ST AND 2ND REVIEWS IS LISTED BELOW. PLEASE SEE |
| | SEC. 403.1.1 FBC PLUMBING. THE TOTAL OCCUPANT LOAD 0F |
| | 154 SHALL BE DIVIDED IN HALF. TO DETERMINE THE NUMBER |
| | OF FIXTURES, THE FIXTURE RATIO OR RATIOS FOR EACH |
| | FIXTURE TYPE SHALL BE APPLIED TO THE OCCUPANT LOAD OF |
| | EACH SEX IN ACCORDANCE WITH TABLE 403.1 FBC P. BUSINESS |
| | OCCUPANCY WITH 154 OCCUPANTS REQUIRES 3 MALE AND 3 |
| | FEMALE WATER CLOSETS, AND 2 MALE AND 2 FEMALE |
| | LAVATORIES- TABLE 403.1. PLEASE NOTE SHEET G100 |
| | SPECIFIES 176 OCCUPANTS. WHICH OCCUPANT LOAD IS |
| | CORRECT? |
| | |
| | 1) FAILED. G110: THE PLAN APPEARS TO SHOW THE OCCUPANT |
| | LOAD OF THE STORY HAS INCREASED OVER 20%. REFER TO SEC. |
| | 810.1 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS |
| | IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED |
| | NUMBER OF PLUMBING FIXTURES. PLEASE NOTE THAT DRINKING |
| | FOUNTAINS AND SERVICE SINKS ARE REQUIRED FOR B |
| | OCCUPANCIES. THE CALCULATIONS AND PLANS ARE NOT IN |
| | COMPLIANCE WITH TABLE 403.1 FBC WHICH REQUIRES A |
| | MINIMUM OF 3 MALE WATER CLOSETS EACH AND 2 MALE AND 2 |
| | FREMALE LAVATORIES EACH. PLEASE NOTE SEPARATE |
| | FACILITIES ARE REQUIRED FOR MALE AND FEMALE USE- SEC. |
| | 403.2 |
| | |
| | NEW COMMENT. |
| | |
| | 2) SHEET P200 WAS NOT UPLOADED FOR REVIEW WITH THE 2ND |
| | SUBMITTAL. THE SHEET IS NAMED P200 IN PROJECT DOX BUT |
| | IS ACTUALLY SHEET P201 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |